Mr. Bernard P. Orlan June 26, 2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and Finance (M833) ArCPrpiectNqa5-19125-0291
TYOCC^centration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Indoor concentrations of CO, CO2 and TVOCs were within applicable standards and
guidelines.
2. Fifty (50) of the indoor measurements for temperature were above the range of 73 °F to 79°F
(at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the
summer season.
3. All of the indoor measurements for relative humidity were within ASHRAE recommended
range of 30 to 60 percent for occupant comfort.
4. Nine of the indoor measurements for respirable particulates were above the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter. Five (5) of the indoor measurements were above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or
212.
Sincerely,
ATC ASSOCIATES INC.
'Yiaimis Efstathiou
Senior Project Manager
Attachment
CONFIDENTIAL, CITY_21MC1OO_OO3462998
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259546
OCR can misread numbers and units. Confirm readings against the page image before using them.