Indoor air quality report, High School of Economics and Finance,

Machine-extracted title · confidence 42%

ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.

NYC-WTC_000396559–000396562
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P, Orlan May 17,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 72.3 °F to 81.6 °F. Nine (9) of the indoor measurements collected were below and thirty-seven (37) measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements ranged from 67.5 °F to 77.5°F.

Relative Humidity

The relative humidity indoors ranged from 30.5 percent to 38.9 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 30.3 to 35.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 412 ppm to 1269 ppm. Two (2) of the indoor measurements for CO? were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 541 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1241 ppm (background level + 700 ppm). The highest reading (1269 ppm) was measured in room 204 at 9:31 AM with 25 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.

Respirable Particulates (PM2.5)

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 31 pg/m^ with an average of 15 pg/m^- All of the indoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 42 pg/m^ to 76 pg/m^ with an average of 56 pg/m^ •

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_002891479

NYC-WTC_000396561

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000396561Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259417

Indoor air quality measurements collected May 16, 2002 for BOE program.

Similar indexed content

NYC-WTC_000396667

IAQ measurements collected May 30, 2002 for BOE IAQ program.

Similar indexed content

NYC-WTC_000384975

ATC IAQ measurements at 100 Trinity Place (HS of Economics and Finance) for BOE in May 2002.

Similar indexed content

NYC-WTC_000396575

ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.

Similar indexed content

NYC-WTC_000180045

Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.

Similar indexed content

Compare copies and versions →