Mr. Bernard P. Orlan May 17, 2002
Indoor Air Quality Assessment Page 3
H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291
Real-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmental measurements
consisiing of ninety-four (94) inside the school building and twelve (12) outdoors. Field data
sheets are found in the Attachment. Readings were collected between morning to evening. The
results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 72.3 °F to 81.6 °F. Nine (9) of the
indoor measurements collected were below and thirty-seven (37) measurements were above the
range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-
1992 during the summer season. The outdoor temperature measurements ranged from 67.5 °F to
77.5°F.
Relative Humidity
The relative humidity indoors ranged from 30.5 percent to 38.9 percent. All of the indoor
measurements for relative humidity were within the ASHRAE recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity ranged from 30.3 to 35.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 412 ppm to 1269 ppm. Two (2) of the
indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level. The outdoor (background)
CO2 concentration was 541 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1241 ppm (background level + 700 ppm). The highest reading (1269 ppm) was
measured in room 204 at 9:31 AM with 25 occupants. Levels above the recommended maximum
do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from
1 ppm to 2 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 31 pg/m3 with an
average of 15 pg/m^- All of the indoor measurements for respirable particulates were below the
NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or
less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals and children. The respirable concentrations outdoors ranged between 42
pg/m^ to 76 pg/m^ with an average of 56 pg/m^ ■
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.