Mr. Bernard P. Orlan June 3, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 77.4 °F to 83.4 °F. Eighty -seven (87) of the indoor measurements for temperature were above and seven of the measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 77.1 °F to 89.0 °F.
Relative Humidity
The relative humidity indoors ranged from 39.4 percent to 59.8 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 58.2 to 68.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 504 ppm to 1287 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 536 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1236 ppm (background level + 700 ppm). The highest concentrations were recorded in room 306, 308 at about 15:28 PM with 14,8 occupants respectively. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CarbonA^noxideConcentratipn
Carbon monoxide concentrations indoors were Ippm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to 2 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 31 pg/m^ with an average of 11 pg/m^- None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 29 pg/m3 to 74 pg/m^ with an average of 47 pg/m^ •
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CONFIDENTIAL, CITY_21MC1OO_OO3462725 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259485
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259479
ATC IAQ measurements report for May 30, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180045
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396671
IAQ field measurements collected Jun 3, 2002 for IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396559
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219896
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223584
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384975
ATC IAQ measurements at 100 Trinity Place (HS of Economics and Finance) for BOE in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396620
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180045
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259479
ATC IAQ measurements report for May 30, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259519
ATC IAQ measurements report for June 17, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements report for May 30, 2002 at the school.
Similar indexed content
Indoor air quality measurements collected May 16, 2002 for BOE program.
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
Similar indexed content
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similar indexed content
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
Similar indexed content