Mr. Bernard P. Orlan May 17, 2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and Finance tM833) ATC Project No. 15-19125-0291
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following;
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FIIXDINGS
Based on the real-time measurements, the following findings are presented:
1. Indoor concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Nine (9) of the indoor measurements collected were below and thirty-seven (37)
measurements were above the range of 73 to 79°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE
recommended range of 30 to 60 percent for occupant comfort.
4. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest reading (1269 ppm) was measured in room 204 at 9:31 AM with 25 occupants.
Levels above the recommended maximum do not indicate a health risk. Carbon dioxide
measurements are used as an indicator of available outdoor air. The primary source of CO2
indoors is occupant respiration.
5. All of the indoor measurements for respirable particulates were below the NPAAQS of 65
pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter or the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension 211
or212.
Sincerely,
/I TCASSOCIA TES INC.
Revi,
Amel Javay / James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene
Attachment
CONFIDENTIAL, CITY_21MC100_003462601
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259420
OCR can misread numbers and units. Confirm readings against the page image before using them.