Mr. Bernard P, Orlan May 21, 2002 Indoor Air Quality Assessment Page 3 H.S. c f Economics and Finance (M833) ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting oi' eight}-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Te/np:’raliire
Indoo' dry bulb temperature measurements ranged from 63.1 4- to 80.1 °F. Twenty-two (22) of the irdoor measurements for temperature collected were below and twenty-one (21) indoor temperature measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 57.9 °F to 69.6°F.
Relati ve Humidily
The relative humidity indoors ranged from 17.6 percent to 34.5 percent. Sixty-six (66) of the indoor measurements for relative humidity' were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 16.0 to 21.7 pcrccr.t.
Carbcn Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 584 ppm to 1460 ppm. Sixteen (16) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 502 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1202 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Cqr^n Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 to 2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations also ranged from 0 ppm to 2 ppm for all readings.
Rexpii -able Particidates (PM2,5)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 75 pg/m^ with an average of 10 pg/m^- Two (2) of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micro neters or less in aerodynamic diameter. Three (3) of the indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 18 pg/m^ to 53 pg/m^ with an average of 37 pg/m- ■
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
CONFIDENTIAL, CITY_21MC100_0 03462620 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259427
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259200
Indoor air quality measurements taken April 18, 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259487
ATC summary of IAQ measurements collected June 4, 2002 at the school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384991
ATC indoor air quality measurements at the referenced school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259196
ATC indoor air quality measurements conducted April 17, 2002 for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259286
May 1, 2002 IAQ measurements for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259523
ATC IAQ measurements report for June 18, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385071
ATC IAQ measurements collected on June 3, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259358
Indoor air quality measurements collected May 7, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259272
April 29–30, 2002 IAQ measurements for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259487
ATC summary of IAQ measurements collected June 4, 2002 at the school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259204
ATC report of IAQ measurements collected April 19, 2002 for BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259244
ATC report of IAQ measurements collected April 25, 2002 for BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384928
IAQ measurements collected May 14, 2002 for school project.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements taken April 18, 2002 for BOE program.
Similar indexed content
ATC summary of IAQ measurements collected June 4, 2002 at the school.
Similar indexed content
ATC indoor air quality measurements at the referenced school, May 2002.
Similar indexed content
ATC IAQ measurements report for June 13, 2002 at the school.
Similar indexed content
ATC indoor air quality measurements conducted April 17, 2002 for BOE review.
Similar indexed content