Mr. Bernard P. Orlan April 22, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291
Real-Time Environmental measurements
ATC collected ninety-nine (99) sets of real-time environmental measurements consisting of eighty-seven (87) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began in the morning and concluded in the afternoon. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 83.2 °F to 88.7 °F. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 83.2 to 88.7 °F.
Relative Humidity
The relative humidity indoors ranged from 32.6 percent to 38.9 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 36.5 to 37.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 415 ppm to 672 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 517 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1217 ppm (background level + 700 ppm), Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 14 pg/m^ with an average 22 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the eighty-seven (87) instantaneous indoor readings was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 13 pg/m- to 45 pg/m^ with an average of 30 pg/m^. Six (6) of the twelve (12) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
CONFIDENTIAL, CITY_21MC1OO_OO3462315 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259206
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384928
IAQ measurements collected May 14, 2002 for school project.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384258
Chain-of-custody document for potable water samples collected at 104 East 25th Street.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259188
IAQ measurements conducted April 15, 2002 at the referenced school for BOE evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383088
IAQ measurements at High School of Economics and Finance conducted April 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259145
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259507
ATC IAQ measurements report for June 11, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383107
Indoor air measurements collected April 17, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259244
ATC report of IAQ measurements collected April 25, 2002 for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384928
IAQ measurements collected May 14, 2002 for school project.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259192
ATC report of IAQ measurements collected April 16, 2002 for NYC BOE program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
Similar indexed content
NYC-WTC_000384928
IAQ measurements collected May 14, 2002 for school project.
Similar indexed content
Indoor air quality measurements collected May 13, 2002 for BOE.
Similar indexed content
ATC indoor air quality measurements collected May 14, 2002.
Similar indexed content