NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗ATC report of IAQ measurements collected April 19, 2002 for BOE.
NYC-WTC_000259204–000259207OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 22, 2002 Indoor Air Quality Assessment Page 2 H.S. of Economics and Finance (M833) ATC Protect No. 15-19125-0291
The lesults of the sampling represent condition.; found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the EOF as a guide to assess the need for further improvements in current indoor air quali y control activities.
EVAHJATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as office; and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
I'eritilation for Acceptable Indoor Air Quality (ASHRAE 62 J999). American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); nermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality' will be achieved at all times.
TABLE I TARGET GUIDELINES FOR INDOOR AIR QUALITY PAR.AMETERS EVALUATED
PARAMETER TARGETLEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS)____________ Res])irable 65 micrograms per cubic meter USEPA NPAAQS Part culates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Terr perature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Rek five Humidity 30 - 60 % ASHRAE 55 Toti 1 Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPA/.QS = National Primary Ambient-Air Quality Standard AIHA == American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC1OO_OO3462314 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259205
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384928
IAQ measurements collected May 14, 2002 for school project.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384258
Chain-of-custody document for potable water samples collected at 104 East 25th Street.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259188
IAQ measurements conducted April 15, 2002 at the referenced school for BOE evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383088
IAQ measurements at High School of Economics and Finance conducted April 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259145
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259507
ATC IAQ measurements report for June 11, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259161
Indoor air quality data collection at Trinity Place site, April 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259149
ATC IAQ measurements collected March 25, 2002 for BOE program.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384163
IAQ report covering measurements and signatures for school site.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396620
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259157
ATC notes and observations for IAQ measurements at the school, March 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223584
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
Similar indexed content
NYC-WTC_000384928
IAQ measurements collected May 14, 2002 for school project.
Similar indexed content
Indoor air quality measurements collected May 13, 2002 for BOE.
Similar indexed content
ATC indoor air quality measurements collected May 14, 2002.
Similar indexed content