Mr. Bernard P. Orlan April 9, 2002 Indoor Air Quality Assessment Page 2 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 The -esults of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the E!OE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALIJATION CRITERIA
Currently, there are no regulatory' standards for indoor air quality m non-mdustrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society cf Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHjT4E 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meet ng one, some, or all of the listed values does not assure that acceptable indoor air qualih/ will te achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO 2)____________ above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO)_____________ USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Part culates (PM2.5) of air (gg/m^) 24-hour average 40 p.g/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TV DC) USEP.\ ■■ United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC100_003462183 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259162
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000404462
IAQ measurements at HS of Economics and Finance, April 8, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219378
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384177
IAQ measurements collected March 13, 2002 at High School of Economics and Finance.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402480
Indoor air quality measurements collected on March 14, 2002 for the specified school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402465
Indoor air quality measurements collected at the referenced school in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402495
Indoor air quality measurements collected on March 15, 2002 for the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402533
Indoor air quality measurements collected March 21, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384241
IAQ measurements collected at HS Economics & Finance per BOE request; March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000396591
IAQ measurements collected May 20, 2002 at the referenced school for BOE review.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384886
IAQ report covering measurements at HS Economics and Finance, 100 Trinity Place.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383092
IAQ measurements collected April 16, 2002 for BOE evaluation at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402423
Indoor air quality measurements collected on March 8, 2002 at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404467
IAQ measurements at 100 Trinity Place, performed April 9, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385035
ATC indoor air quality measurements for BOE at HS of Economics and Finance, May 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements at HS of Economics and Finance, April 8, 2002.
Similar indexed content
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
Similar indexed content
NYC-WTC_000384177
IAQ measurements collected March 13, 2002 at High School of Economics and Finance.
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
Similar indexed content
NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
Similar indexed content