Mr. Bernard P. Orlan April 9, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 11:23 A.M. and concluded after 6:02 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 66.7 °F to 77.2 °F. Six (6) of the indoor measurements for temperature were below, eleven (11) measurements were above, and seventy- one (71) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 60.8 to 64.4 °F.
Relative Humidity
The relative humidity indoors ranged from 26.8 percent to 50.4 percent. Six (6) of the indoor measurements for relative humidity were below and eighty-two (82) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 30.7 to 36.6 percent.
Carbon Dioxide Concentration
Carbirn dioxide concentrations indoors ranged from 459 ppm to 1637 ppm. Five (5) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 421 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1121 ppm (background level + 700 ppm). The highest level was measured in the cafeteria at 11:47AM with 200 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were between 1 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 ppm to 4 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 34 pg/m^ with an average 12 pg/m^- All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 33 pg/m^ to 93 pg/m-^ with an average of 59 pg/m^. Three (3) of the outdoor measurements was above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
CONFIDENTIAL, CITY_21MC100_003462184 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259163
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000404462
IAQ measurements at HS of Economics and Finance, April 8, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219378
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384177
IAQ measurements collected March 13, 2002 at High School of Economics and Finance.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402480
Indoor air quality measurements collected on March 14, 2002 for the specified school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402465
Indoor air quality measurements collected at the referenced school in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402495
Indoor air quality measurements collected on March 15, 2002 for the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402533
Indoor air quality measurements collected March 21, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384241
IAQ measurements collected at HS Economics & Finance per BOE request; March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000219378
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259475
ATC indoor air quality measurements report for May 29, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259491
ATC report of IAQ measurements collected June 4, 2002 at the school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396663
ATC IAQ measurements collected May 29, 2002 for IAQ maintenance check.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396679
IAQ measurements collected Jun 4, 2002 for BOE monitoring.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404481
Report of IAQ measurements at High School of Economics and Finance (M833) for BOE in Apr 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements at HS of Economics and Finance, April 8, 2002.
Similar indexed content
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
Similar indexed content
NYC-WTC_000384177
IAQ measurements collected March 13, 2002 at High School of Economics and Finance.
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
Similar indexed content
NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
Similar indexed content