Indoor air quality measurements taken April 18, 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗Indoor air measurements collected May 20, 2002 for BOE IAQ program.
NYC-WTC_000259425–000259428OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P, Orlan May 21, 2002 Indoor Air Quality Assessment Page 2 ’f Economics and Finance (M833) ATC Project No. 15-19125-0291 The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in thi.s report should be used by the BOE as a guide to assess the need for further improvements in current indoor air qualit/control activities.
EVAJ.UATION CRITERIA
Currently, there are no regulatory' standards for indoor air quality in non-industrial buildings, such «'.s offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999). American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Condition.'; for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Qua/ily Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO;.) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PMy.y) of air (pg/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temoeraturc Summer: 73-79°F at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH Relaave Humidity 30 -60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEP/^ = United States Environmental Protection Agency NP.-XAQS = National Primary Ambient-Air Quality Standard AlflA = American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC100_003462619 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259426
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259200
Indoor air quality measurements taken April 18, 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259487
ATC summary of IAQ measurements collected June 4, 2002 at the school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384991
ATC indoor air quality measurements at the referenced school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259196
ATC indoor air quality measurements conducted April 17, 2002 for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259286
May 1, 2002 IAQ measurements for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259523
ATC IAQ measurements report for June 18, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385071
ATC IAQ measurements collected on June 3, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259358
Indoor air quality measurements collected May 7, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259272
April 29–30, 2002 IAQ measurements for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259523
ATC IAQ measurements report for June 18, 2002 at the school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402437
IAQ measurements conducted March 11, 2002 at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383088
IAQ measurements at High School of Economics and Finance conducted April 15, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259483
ATC IAQ report documenting measurements collected June 3, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384959
Indoor air quality measurements collected May 15-16, 2002 for the school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402409
IAQ field report for measurements at the school, part of a program to maintain acceptable IAQ.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements taken April 18, 2002 for BOE program.
Similar indexed content
ATC summary of IAQ measurements collected June 4, 2002 at the school.
Similar indexed content
ATC indoor air quality measurements at the referenced school, May 2002.
Similar indexed content
ATC IAQ measurements report for June 13, 2002 at the school.
Similar indexed content
ATC indoor air quality measurements conducted April 17, 2002 for BOE review.
Similar indexed content