IAQ report, High School of Economics and Finance, Mar 2002

Machine-extracted title · confidence 31%

ATC IAQ measurements collected March 25, 2002 for BOE program.

NYC-WTC_000259149–000259152
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 26, 2002 Indoor Air Quality Assessment Page 3 H.S. jf Economics and Finance (M833)________ ATC ProicctNo. 15-19125-0291 Reai -Time Environmental .Measi remi x is

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eight/-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the /Attachment. Readings began at 10:03 A.M. and concluded after 5:53 P.M. The results are described below.

Tef^emture

Indoc r dry bulb temperature measurements ranged from 63.7 °F to 77.8 °F. Twelve (12) of the indoc r measurements for temperature were below and fourteen (14) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-IS92 during the heating season (wintertime conditions). The outdoor temperature ranged from 40.8 to 47.6 °F.

Humidity

The relative humidity indoors ranged from 19.7 percent to 36.2 percent. Seventy-live (75) of the' indoor measurements for relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 22.3 to 25.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 353 ppm to 1152 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 417 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1117 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements arc used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were between 0 to 2 ppm. These concentrations were below the NP/vAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 ppm to 4 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 27 pg/m3 with an average 7 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and ciildren. The outdoor respirable particulate concentration ranged from 45 pg/m^ to 92 pg/m- with an average of 45 pg/m^. Five (5) of the outdoor measurements were above the NPA/.QS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. fwclvc (12) outdoor reading were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

CONFIDENTIAL, CITY_21MC100_003462139 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259151

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259151Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259145

Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.

Similar indexed content

NYC-WTC_000259204

ATC report of IAQ measurements collected April 19, 2002 for BOE.

Similar indexed content

Compare copies and versions →