NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 3,2002
Indoor Air Quality Assessment Page 3
H.S. of Economics and Finance (M833)________ ATC Protect No. 15-19125-0291
REz\l-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmental measurements
consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data
sheets are found in the Attachment. Readings were collected between morning to evening. The
results are described below.
Temperatitre
Indoor dry bulb temperature measurements ranged from 77.4 ®F to 83.4 °F. Eighty -seven (87)
of the indoor measurements for temperature were above and seven of the measurements were
within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE
Standard 55-1992 during the summer season. The outdoor temperature measurements ranged
from 77.1 °F to 89.0 °F.
Relative Humidity
The relative humidity indoors ranged from 39.4 percent to 59.8 percent. All of the indoor
measurements for relative humidity were within the ASHRAE recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity ranged from 58.2 to 68.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 504 ppm to 1287 ppm. One (1) of the indoor
measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 536 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1236 ppm (background level + 700 ppm). The highest concentrations were recorded in room
306, 308 at about 15:28 PM with 14,8 occupants respectively. Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of
available outdoor air. The primary source of CO2 indoors is occupant respiration.
CarbonMonoxideConcentration
Carbon monoxide concentrations indoors were Ippm. These concentrations were below the
NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to
2 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 31 pg/m^ with an
average of 11 pg/m^- None of the indoor measurements for respirable particulates were above
the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers
or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^
for sensitive individuals and children. The respirable concentrations outdoors ranged between
29 pg/m3 to 74 pg/m3 with an average of 47 pg/m^ •
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.