NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 3, 2002
Indoor Air Quality Assessment Page 4
H.S^ofEcpnpmics^dFinanceTM^^^ ATC Project No. 15-19125-0291
T7OC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Indoor concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Eighty -seven (87) of the indoor measurements for temperature w ere above and seven of the
measurements were within the range of 73 to 79°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE
recommended range of 30 to 60 percent for occupant comfort.
4. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest concentrations were recorded in room 306, 308 at about 15:28 PM with 14,8
occupants respectively. Levels above the recommended maximum do not indicate a health
risk. Carbon dioxide measurements are used as an indicator of available outdoor air.
5. None of the indoor measurements for respirable particulates were above the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext 290
Sincerely,
/I TC ASSOCIA TES INC.
Prasad Doddapaneni ’
Senior Project Manager
Attachment
CITY_21MC100_002882382