Mr. Bernard P. Orlan March 7, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Proicct No. 15-19125-0291 Real-Time Environmental measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:07 A.M. and concluded after 14:45 P.M. The results are described below.
Temperalure
Indoor dry bulb temperature measurements ranged from 59.9 °F to 78.9 °F. Twenty-five (25) of the indoor measurements were below and nineteen (19) were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 46 to 63.3 °F.
Relative Humidity
The relative humidity indoors ranged from 22.5 percent to 38.5 percent. Fifty-two (52) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Thirty-six (36) measurements were within the ASHRAE recommended range. The outdoor relative humidity ranged from 21.8 to 29.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 407 ppm to 1194 ppm. Five (4) of the indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 439 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1139 ppm (background level + 700 ppm). The highest reading (1194 ppm) was measured in stairwell A 8^^ floor at 1:09 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 to 4 ppm.
Respirable Particulates (PM2_§)
Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 48 pg/m^ with an average 7 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The PM2.5 average concentration was also below the USEPA recommended concentration of 40 pg/m3 for sensitive individuals / children. Please note that two readings indicate 46pg/m3 and 48 pg/m^ in locations staircase B 9^ floor and staircase B 7^^ floor respectively. The outdoor respirable particulate concentration ranged from 27 pg/m^ to 69 pg/m^ with an average of 53 pg/m3.
CITY_21MC100_000467789 NYC-WTC_000384113
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402409
IAQ field report for measurements at the school, part of a program to maintain acceptable IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259024
IAQ measurement report for H.S. of Economics and Finance (Mar 7, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404481
Report of IAQ measurements at High School of Economics and Finance (M833) for BOE in Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384250
Chain-of-custody for potable water sampling at Trinity Place site, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384254
Chain-of-custody for potable water samples taken at 104 East 25th Street location.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384900
May 9-10 IAQ measurements at the school, part of BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384125
Indoor air quality report for school, measurements and professional signatures.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402538
Indoor air quality measurements collected March 22, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384886
IAQ report covering measurements at HS Economics and Finance, 100 Trinity Place.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384246
Indoor air quality measurements collected on March 22, 2002 at HS Economics & Finance.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000404467
IAQ measurements at 100 Trinity Place, performed April 9, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402409
IAQ field report for measurements at the school, part of a program to maintain acceptable IAQ.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383193
IAQ measurements collected April 29, 2002 for BOE at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259024
IAQ measurement report for H.S. of Economics and Finance (Mar 7, 2002).
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384149
ATC indoor air quality report documenting measurements at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ field report for measurements at the school, part of a program to maintain acceptable IAQ.
Similar indexed content
NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000259024
IAQ measurement report for H.S. of Economics and Finance (Mar 7, 2002).
Similar indexed content
NYC-WTC_000404481
Report of IAQ measurements at High School of Economics and Finance (M833) for BOE in Apr 2002.
Similar indexed content
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
Similar indexed content