NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, ATC, 2002

Machine-extracted title · confidence 28%

ATC indoor air quality report documenting measurements at the referenced school.

NYC-WTC_000384149–000384152
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 12, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:05 A.M. and concluded afterl4:58 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 56,1 °F to 70.6 °F. Twenty five (25) of the indoor measurements were below and sixty three (63) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 40.0 to47.0 °F.

Relative Humidity

The relative humidity indoors ranged from 16.8 percent to 37.3 percent. Eighty-four (84) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Four (4) measurements were within the ASHRAE recommended range. The outdoor relative humidity ranged from 15.8 to 22.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 64 ppm to 1321 ppm. All indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concenfration was 746 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1446 ppm (background level + 700 ppm). The highest reading (1321 ppm) was measured in Room #410 approximately at 9:03 AM. Please note that hallway was occupied by approximately 17 people. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were between 1 to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 to 4 ppm.

Respirable Particulates (PM2_s)

Respirable particulate concentrations* indoors ranged between 3 ug/m^ to 71 pg/m^ with an average 10 pg/m^- Two (2) of the eighty-eight (88) instantaneous measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The indoor PM2,5 average concentration was 10 pg/m^ also below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration ranged from 20 pg/m^ to 112 pg/m^ with an average of 55 pg/m^. Three (3) of the outdoor measurements were above the NPAAQS of 65

CITY_21MC100_000467834 NYC-WTC_000384151

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384151Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402437

IAQ measurements conducted March 11, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000259062

ATC report summarizing IAQ measurements for the High School of Economics and Finance at 100 Trinity Place, March 2002.

Similar indexed content

Compare copies and versions →