Indoor air quality report, ATC, 2002

Machine-extracted title · confidence 28%

ATC indoor air quality report documenting measurements at the referenced school.

NYC-WTC_000384149–000384152
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 12,2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 pg/m^ (24-hour average) and nine (9) outdoor measurements are above the USEP.A. recommended concentration of 40 pg/m^ for sensitive individuals I children.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor 'fVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Eighty-four (84) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Four (4) measurements were within the ASHRAE recommended range. 3. Twenty five (25) of the indoor measurements were below and sixty three (63) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. Two (2) of the eighty-eight (88) instantaneous measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The indoor PM2 5 average concentration was 10 pg/m^ also below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education.

If you have any questions about this report, please call (212) 353-8280, extension 356 or 212.

Sincerely, J TCASSOCIA TES INC Reviewed by: zQ

Prasad Doddapaneni ’ James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_2 IMCl 0 Ci_0 0 0 4 6 7 8 3 5 NYC-WTC_000384152

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384152Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402437

IAQ measurements conducted March 11, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000259062

ATC report summarizing IAQ measurements for the High School of Economics and Finance at 100 Trinity Place, March 2002.

Similar indexed content

Compare copies and versions →