IAQ report, High School of Economics and Finance, May 2002

Machine-extracted title · confidence 33%

Indoor air measurements collected May 8, 2002 for BOE IAQ program.

NYC-WTC_000259372–000259375
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 9, 2002 Indooi Air Quality Assessment Page 4 H.S. of Economics and Finance (M833) ATC Proiect No. 15-19125-0291

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

Durinj; this assessment, ATC noted the following: • TliC interior of the building appeared clean and free of dust and debris; • Tlie building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1,Indoor concentrations of CO and TVOCs were below applicable standards and guidelines. 2.Seventy-four (74) of the indoor measurements collected were above and fourteen (14) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. Tivo (2) of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1375 ppm) was measured in room # 305 around 2:48 P.M. with 18 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. 5. All of the indoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sc nsitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, A TC 4SSOCIA TES INC. Reviewed by:

uXmel Ja-i^y James R. Cohn, CIH, CSP Senior PpMect Manager Regional Manager, Industrial Hygiene

Attac ament

CONFIDENTIAL, CITY_2IMCI00_003462510 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259375

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259375Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259184

ATC Associates report on IAQ measurements taken April 12, 2002 at the school for BOE review.

Similar indexed content

NYC-WTC_000259358

Indoor air quality measurements collected May 7, 2002 for BOE program.

Similar indexed content

NYC-WTC_000259330

Indoor air measurements collected May 3, 2002 for the BOE IAQ program.

Similar indexed content

NYC-WTC_000259344

ATC indoor air quality measurements conducted May 6, 2002 for BOE.

Similar indexed content

Compare copies and versions →