Indoor air quality measurements collected March 26, 2002 for school.

NYC-WTC_000259153–000259156
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. E emard P. Orlan March 27, 2002 Indoc r Air Quality Assessment Page 4 U.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 2^-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • Tre interior of the building appeared clean and free of dust and debris; • Tre building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. C uncentrations CO2, CO and TVOCs were below applicable standards and guidelines. 2. Fifteen (15) of the indoor measurements for temperature were below, ten (1) measurements were above, and sixty-three (63) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Forty-four (44) of the indoor measurements for relative humidity were below and forty-four (44) were within the ASHRAE recommended range of 30 to 60 percent for occupant ciimfort. 4. Nune of the indoor measurements for PM 2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter 01 the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. None of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour at erage concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the twelve (12) instantaneous outdoor reading was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is cur pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or2E.

Sincerely, Reviewedby^ /I TG^iSSOCIA TES INC. \ -t-v. /’Mel JavaL James R. Cohn, CIH, CSP Senio ■ ProjWt Manager Regional Manager Industrial Hygiene Division

/Attachment

CONFIDENTIAL, CITY_21MC100_003462155 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259156

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259156Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259157

ATC notes and observations for IAQ measurements at the school, March 2002.

Similar indexed content

NYC-WTC_000259180

IAQ measurements collected April 11, 2002 for BOE program.

Similar indexed content

Compare copies and versions →