IAQ report, High School of Economics and Finance, Apr 2002

Machine-extracted title · confidence 41%

Indoor air quality measurements taken April 18, 2002 for BOE program.

NYC-WTC_000259200–000259203
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 19, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATCProiectNpa5a9125;029i Real-Time Environmental Measurements

ATC collected one-hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began in the morning and concluded m the afternoon. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 82 °F to 86.9 °F. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 82 to 85.9 °F.

RelatiyeHumidity

The relative humidity indoors ranged from 62.1 percent to 65.7 percent. All of the indoor measurements for relative humidity were above the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 62.1 to 65.9 percent.

Carban Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 516 ppm to 1261 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COo concentration was 660 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1360 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carban Monoxide Concentridipn

Carbon monoxide concentrations ranged from 2 ppm to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm to 3 ppm.

Respirable Particulates iPM2 S)

Respirable particulate concentrations* indoors ranged between 17 pg/m^ to 35 pg/m^ with an average 24 pg/m^ • All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 60 pg/m^ to 65 pg/m^ with an average of 62 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CONFIDENTIAL, CITY_21MC100_003462300 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259202

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259202Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259196

ATC indoor air quality measurements conducted April 17, 2002 for BOE review.

Similar indexed content

NYC-WTC_000259208

Report of indoor air quality measurements collected April 22, 2002 for BOE.

Similar indexed content

NYC-WTC_000259244

ATC report of IAQ measurements collected April 25, 2002 for BOE.

Similar indexed content

Compare copies and versions →