Mr. Bernard P. Orlan April 29, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATCPrpiectNoa5-19125-0291
Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 68.5°F to 77.0°F. Twenty nine (29) measurements were below and fifty nine (59) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 58.0 °F to 67.4 °F.
Relative Humidity
The relative humidity indoors ranged from 18.8 percent to 27.4 percent. All of the indoor measurements for relative humidity were bellow the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 15.8 to 19.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 444 ppm to 1611 ppm. Two of the indoor measurements for CO2 were high and these readings were detected in Staircase A to 4th poor indicating CO2 concentration of 1498 ppm with four (4) occupants and Room # 410 indicating CO2 concentration of 1611 ppm with twenty six (26) occupants , These measurements were collected at approximately 10:38 AM. Eighty six indoor (86) measurements below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 474 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1174 ppm (background level -I- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Car^mMonojddeCpncetUratipn
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 36 pg/m^ with an average 8 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2..5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 20 pg/m^ to 65 pg/m^ with an average of 35 pg/m^.
CONFIDENTIAL, CITY_21MC100_003462388 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259260
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000383179
IAQ measurements conducted April 26, 2002 for BOE at the school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404562
IAQ measurements collected on Apr 26, 2002; BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259503
ATC IAQ measurements report for June 7, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223588
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396687
ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396695
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259272
April 29–30, 2002 IAQ measurements for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384163
IAQ report covering measurements and signatures for school site.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179976
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259272
April 29–30, 2002 IAQ measurements for BOE program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219870
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396707
ATC IAQ measurements collected June 13, 2002 under BOE directive for IAQ maintenance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383179
IAQ measurements conducted April 26, 2002 for BOE at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385083
ATC IAQ measurements collected June 6, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396671
IAQ field measurements collected Jun 3, 2002 for IAQ monitoring.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000383179
IAQ measurements conducted April 26, 2002 for BOE at the school.
Similar indexed content
NYC-WTC_000404562
IAQ measurements collected on Apr 26, 2002; BOE program.
Similar indexed content
ATC IAQ measurements report for June 7, 2002 at the school.
Similar indexed content
NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
Similar indexed content
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 23, 2002.
Similar indexed content