Mr. Bernard P. Orlan April 30, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ArCProiecLNoM5J.9125;029i Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 72.1 °F to 75.6 °F. Eighteen (18) measurements were below and seventy (70) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 65.3 °F to 74.3 °F.
Relative Humidity’
ITie relative humidity indoors ranged from 27.1 percent to 65 percent. Forty-six (46) of the indoor measurements for relative humidity were below, one (1) was above, and forty-one (41) measurement were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 28.2 to 34.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 456 ppm to 1402 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 519 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1219 ppm (background level + 700 ppm). The highest reading (1402 ppm) was measured on the 3rd floor staircase A at 9:15 AM with 31 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 2 ppm to 4 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm to 3 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 16 pg/m^ with an average 11 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 6 pg/m^ to 36 pg/m^ with an average of 22 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CONFIDENTIAL, CITY_21MC100_003462403 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259274
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259479
ATC IAQ measurements report for May 30, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180045
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223584
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259421
ATC test results for IAQ program at 100 Trinity Place; May 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259483
ATC IAQ report documenting measurements collected June 3, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396707
ATC IAQ measurements collected June 13, 2002 under BOE directive for IAQ maintenance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383193
IAQ measurements collected April 29, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259503
ATC IAQ measurements report for June 7, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384959
Indoor air quality measurements collected May 15-16, 2002 for the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396695
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259258
ATC report of IAQ measurements collected on April 26, 2002 for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259503
ATC IAQ measurements report for June 7, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385083
ATC IAQ measurements collected June 6, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396707
ATC IAQ measurements collected June 13, 2002 under BOE directive for IAQ maintenance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219870
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements report for May 30, 2002 at the school.
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
Similar indexed content
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
Similar indexed content
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
Similar indexed content
ATC test results for IAQ program at 100 Trinity Place; May 17, 2002.
Similar indexed content