Mr. Bernard P. Orlan June 14,2002
Indoor Air Quality Assessment Page 3
H.S. of Economics and Finance (M833) ATCProiectNo. 15-19125-0291
REAL-TIME ENVIRONMENTAL MEASUREMENTS
ATC collected one hundred and six (106) sets of real-time environmental measurements
consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data
sheets are found in the Attachment. Readings were collected between morning to evening. The
results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 73.9 °F to 80.1 °F. Sixteen (16) of the
indoor measurements for temperature were above and none of the measurements were below the
range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-
1992 during the summer season. The outdoor temperature measurements ranged from 68 °F to
75.6 °F.
Relative Humidity
The relative humidity indoors ranged from 38.0 percent to 52.9 percent. All of the indoor
measurements for relative humidity were within ASHRAE recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity ranged from 49.6 to 52.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 524 ppm to 1311 ppm. Nine (9) of the
indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level. The outdoor (background)
CO2 concentration was 501 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1201 ppm (background level + 700 ppm). The highest concentration (1311 ppm)
was recorded in room 307 around 11:55 AM with 27 occupants. Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of
available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from 1 ppm to 2 ppm.
Respirable Particulates (PM2 j)
Respirable particulate concentrations* indoors ranged between 4 gg/m^ to 38 gg/m^ with an
average of 11 gg/m^- None of the indoor measurements for respirable particulates were above
the NPAAQS of 65 gg/m^ 24-hour average concentration of particulate matter 2.5 micrometers
or less in aerodynamic diameter and the USEPA recommended concentration of 40 gg/m^ for
sensitive individuals and children. The respirable concentrations outdoors ranged between 65
gg/m3 to 88 gg/m3 with an average of 75 gg/m^ •
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.