Mr. Bernard P. Orlan May 16, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Proiect No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 71.1 °F to 82.2 °F. Ten (10) of the indoor measurements collected were below and twenty (20) measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 64.6 °F to 73.6°F.
Relative Humidity
The relative humidity indoors ranged from 24.6 percent to 40.1 percent. Twenty-one (21) of the indoor measurements for relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 20.1 to 29.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 401 ppm to 1261 ppm. Five (5) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 510 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1210 ppm (background level + 700 ppm). The highest reading was measured in room 509 at 2:16 PM with 22 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 36 pg/m^ with an average of 16 pg/m^- All of the indoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 14 pg/m3 to 33 pg/m^ with an average of 26 pg/m^- * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002882205
NYC-WTC_000384961
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396671
IAQ field measurements collected Jun 3, 2002 for IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396559
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396707
ATC IAQ measurements collected June 13, 2002 under BOE directive for IAQ maintenance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223584
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385049
ATC May–June 2002 IAQ report correspondence with BOE about school's air quality.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396620
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404489
IAQ measurements conducted at the referenced school as part of BOE program (Apr 16, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259421
ATC test results for IAQ program at 100 Trinity Place; May 17, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396671
IAQ field measurements collected Jun 3, 2002 for IAQ monitoring.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396707
ATC IAQ measurements collected June 13, 2002 under BOE directive for IAQ maintenance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384928
IAQ measurements collected May 14, 2002 for school project.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383165
ATC notes IAQ measurements performed April 25, 2002 for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ field measurements collected Jun 3, 2002 for IAQ monitoring.
Similar indexed content
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
Similar indexed content
ATC IAQ measurements collected June 13, 2002 under BOE directive for IAQ maintenance.
Similar indexed content
NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
Similar indexed content
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
Similar indexed content