NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, High School of Economics and Finance, Apr 2002

Machine-extracted title · confidence 41%

Indoor air quality measurements taken April 18, 2002 for BOE program.

NYC-WTC_000259200–000259203
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 19, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debns; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of CO2, CO and TVOCs were below applicable standards and guidelines. 2. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for relative humidity were above the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. All of the indoor measurements for respirable particulates were below the NPAAQS of 6:5 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, J TC ASSOCIA TES INC. Reviewed by:

Prasad Doddapaneni James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CONFIDENTIAL, CITY_21MC100_003462301 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259203

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259203Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259196

ATC indoor air quality measurements conducted April 17, 2002 for BOE review.

Similar indexed content

NYC-WTC_000259208

Report of indoor air quality measurements collected April 22, 2002 for BOE.

Similar indexed content

NYC-WTC_000259244

ATC report of IAQ measurements collected April 25, 2002 for BOE.

Similar indexed content

Compare copies and versions →