NYC 9/11 Public Portal Document
ATC Environmental, Inc.
104 East 25th Street
'....J New York, New York 10010
ATC Associates Inc. Approved N.Y. State ELAP #10879
104 East 25th Street ACCREDITED NVLAP Lab Code # 1187
New York, NY 10010 Report Date: 10/23/01
ASBESTOS FIBER ANALYSIS BY TR7\NSMI5SION ELECTRON MICROSCOPY (TEM)
With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDSI
Method; MERA Final Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987
J Sample Identification Analysis Parameters
! 1 ProjecC/Site: 40 Rector Street, 40 Rector St., NY, NY TEM Sample No.: 5741 - 62009
Floorsrj2j_l±i_J^j_J^
Date Received: 10/23/01 Grid Openings Analyzed:__ 4
Project Sample No.: 50-7 Average Grid Opening: 106.00 um
L_J
Air Volume: 1800 liters Total Area Analyzed: 0.0450 nim2
Filter Type: MCE 25 mm diam., Pore Size; 0.45 utn Analytical Sensitivity:22;2 s2n!!n2
Effective Area: 385 mm2 0.0048 s/cc
FIBROUS PARTICULATES ANALYZED
Mumber Observed CONCENTRATION
Total
lJ single Matrix Total. Struct. Filter Air
Fibers Bundles Clusters Struct. Struct. >=5um Struct/min2 Struct/cc nqm/m3
Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Ambiguous 0 0 0 0 0 0 0.0 0.0000 0
Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 0
Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A
No Identification 0 0 0 0 0 0 0.0 0.0000 N/A
Totals (All Structures) 0 0 0.0 0.0000 N/A
The estimated uncertainty of this analysis is 1 standard deviation.
Non-asbestos fiber i.d. (EDS/SAED); None detected
Amphibole Asbestos Type: None detected
The Analysis was carried out in accordance with the approved TEM method.
This laboratory is in compliance with the quality specified for the method.
Analyzed by: Report Reviewed by:
Roman Peysakhov Michael A. Gorycki, Ph.D.
Director of Electron Microscopy
NYC-WTC_000174904
OCR can misread numbers and units. Confirm readings against the page image before using them.