NYC 9/11 Public Portal Document
ATC Environmental, Inc.
104 East 25th Street
New York, New York 10010
ATC Associates Inc. Approved N.Y. State ELAP #10879
104 East 25th Street ACCREDITED NVLAP Lab Code # 1187
New York, NY 10010 Report Date: 10/23/01
' ' ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM)
!_ i . With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS)
Method: AHERA Final Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987
Samde Identification Analysis Parameters
, Project/Site: 40 Rector Street, 40 Rector St., NY, NY TEM Sample No.: 5741 - 61976
Floors 1t12, 14, 15, 19
' Date Received: 10/23m Grid Openings Analyzed:__ 4
Project Sample No.: 17-14 Average Grid Opening: 106.00 um
Air Volume: 1820 liters Total Area Analyzed: 0.0450 mni2
Filter Type: MCE 25 mm diam.. Pore Size; 0.45 um Analytical Sensitivity; 22.2 s/mm2
Effective Area: 38S mni2 0.0Q47 s/cc
J FIBROUS PARTICULATES ANALYZED
Number Observed CONCENTRATION
Total
Single Matrix Total. Struct. Filter Air
Fibers Bundles Clusters Struct. Struct >=5um Struct/mm2 Struct/cc nqm/m3
Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0
-.j Ambiguous 0 0 0 0 0 0 0,0 0.0000 0
Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 0
Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A
No Identification 0 0 0 0 0 0 0.0 0.0000 N/A
Totals (All Structures) 0 0 0.0 0.0000 N/A
■ The estimated uncertainty of this analysis is 1 standard deviation.
Non-asbestos fiber i.d. (EDS/SAED): None detected
, , Amphibole Asbestos Type: None detected
The Analysis was carried out in accordance with the approved TEM method.
This laboratory is in compliance with the quality specified for the method.
Analyzed by: Report Reviewed by:
l'""}
Roman Peysakhov Michael A. Gorycki, Ph.D.
<3 Director of Electron Microscopy
NYC-WTC_000174900
OCR can misread numbers and units. Confirm readings against the page image before using them.