NYC Law Department release
Independent mirror · updated as the City releases more · v1.2.6
← Document results/7DCAS/Mayor's Office of Emergency Management 7 World Trade Center Amb. Job # S57-5175
Document / 1 page

Generator load test memo for Mayor's Office, August 1999

Machine-extracted title · confidence 95%

Memo from Ambassador Construction Co. regarding a generator load test conducted on August 31, 1999, at the Mayor's Office of Emergency Management, 7 World Trade Center.

NYC-WTC_000174095

Folder label: “Mayor's Office of Emergency Management 7 World Trade Center Amb. Job # S57-5175

Page image
Scanned page image, NYC-WTC_000174095
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

AUG 04 1399 16:35 FR AMBASSADOR CON. TO 6693640 P.01/01

1

AMBASSADOR CONSTRUCTION CO., INC.

August 4, 1999 Mru Walter Weems Silverstein Properties, Inc. 7 World Trade Center New York, NY 10048

RE; Mayor’s Offioi of Emergency Management 7 World Trade Center

Dear Mr. Weems:

The generator load test was conducted on Saturday July 31. 1999.

Tti© following items were found to have minor problems and will be corrected as per the following: 1 The differential pressure controller will be re-programmed on August 4,1999 This will close the building valves and start emergency condenser water system manually as designed. Ri^ssel Electric, the manufacturer of the ATS switches, is aware of the problem with them. Ttjeir engineering pe;rsonal is working on the minor glitch, and as soon as they have r®*’ched a solution the corrective work will be done. They have said it is just a matter of adding some relays. Once this is accomplished, we can then run the load shedding test.

In Cosentini Associates report (attached) the emergency generator were left in the automatic position and is ready to deliver emergency power on demand, therefore the OEM is ready for power emergency. i I If you have any questions regarding this matter please contact us.

very truly yours,

/^^SSADOR OCNSTRUCTION CO.. INC.

WJzZ- Martin Schneider Vice President

MS;am ccf Glenn Pymento / DCAS

317 Madison avenue ■ new york, ny tool? • 212 9221020 • fax 212 949 9792

I

i NYC-WTC_000174095

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000174095Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Engineering memorandum, job 1854, August 1999 · Box 7DCAS

NYC-WTC_000172539

Engineering consultant memorandum dated August 2, 1999 related to 7 World Trade Center Mayor's Office of Emergency Management.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.908

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →