Response to review comments FDNY - PSACl April 22, 1999 Page 3

[Responwi: Not Required.

d. Indicate the new walls dark to match the other floors.

Response: At this point in the project it will be very time consuming to revise all the drawings. This projects where originally to be done separately.

e. Explain the use of partition type 7c at 4* Floor offices and lb at S"" floor offices.

Response: In the 4*. Floor we used FDNY standards and other floors we used DoiTT standards as directed. (Mr. J. McCormick specifically requested this.)

f. Coordinate the door schedule with construction plans, see door 14, met/gl and '/z hr fire rated. Also door 24,27 is 'A hr or I hr FPSC door.

I Response: Will Comply.

g. Explain the use of slab to slab studs, with gypsum board above raised floor and full height insulation around storage room, lunch room, (ICO, offices 04-07, (7C) when at door the use of sill type C and ’/♦” glass panel sidelight will defeat the purpose of this expensive type of insulated partition which requires the removal of raised floor tiles.

[ Response: This is done for acoustic privacy between offices, not between offices and open area.

4. Drawing A-S-2

a. Explain the use of wall sill type B and door sill type A at all offices.

[Response: This is done for acoustic privacy between offices, not between offices and open area.

b. Explain the use of 1 ’A hr FPSC door with partition type 7D at offices 5-2, 5-3.

I Response: The fire enclosure is around the computer room not the offices.

5. Drawing A-S-3 and E-110 Clearly indicate the new / relocated light fixtures, only.

[Response; Will Comply

6. Drawing No. D-1 Explain the design intent and use of 3-layered gypsum board, insulated partition type next to '/<” glass / metal regular partition at the command center.

Response: The Acoustical consultant, Cerrami & Associates set the design criteria for the partitions. In reference to the glass enclosed command center, the entire center acts as a buffer between the data Center and the adjacent office space. In addition, FDNY specifically requested the glass enclosure.

\wBWYtniciMtPMMecT8U7iM\i I MTCOOcsicaaBsuia'oiinwssroNW to submittal m 4 anoc

Swankc Hayden Connell LtdJSwanke Hayden ConnclIMi Partners LLP 295 Lafayette Street, New York, New York 10012 212 226 9696, Fax 212 219 0059

NYC-WTC_000172345

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000172345Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Fax cover sheet, OEM design proposal, June 1998 · Box 7DCAS

NYC-WTC_000171248

Cover sheet for a fax transmission regarding architectural and engineering design services for the Mayor's Office of Emergency Management at 7 World Trade Center.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.904

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →