Nov-10-98 03:IIP VIKONICS 201 641 7728 P . 05

MAYOR'S OITICEOl- IJ^ERGENCY MANACEMENT CONDUITSI'.CURri'Y SYSTEM SI IT'ITICAriON

2.1 General Requirements

The contractor will supply all materials and labor required to complete the described. All work is to be performed in accordance with applicable building codes. Materials specified herein (by Manufacturer and Model number) arc the only approved materials. All wire used will be UL and NYC approved and as specified. All installation is to be performed to Msuiufacturcr's instructions. The contractor shall maintain a set of redline drawing.^ showing any approved deviations from th.e original contract drawings. The drawings arc to he submitted to Vikonics fifteen (15) days after completion of the work. 22 Contractor Requirements

The requirements are detailed in the following paragraphs. The contractor must provide evidence of compliance to the requirements. At a minimum, the Contractor is required to check continuity of all cables installed by the Contractor. All work that is to be concealed must be inspected, tested, and approved before concealment, All required tests are to be conducted by the contractor and the results provided with notification that the ia.sk is ready for verification. The contractor shall provide a minimu.m of 24 hours notice of inspections to be performed. All cables must be identified with pennanent markers per the numbers in the wiring tables. Markers are to be applied 6" from the cable ends and be visible in the terminating enclosure. Service loops (12” minimum in excess of tcmiination lengths) are to be provided at both ends of cables. Note that fiberoptic cable requires special handling and bend radii. 'fhc sensor cable is to be installed in every conduit except Power between the 2.3"' floor and both the T* floor and the roof radio room. The sensor cable is to be connected a.s one loop for each set going from the 23'** floor, If an odd number of conduits are to be protected then on conduit will contain two sensor cables. See Figure 2.2

23 Fiberoptic Conduit Security System Specifications and InsUilbtion Gukidinc

The following paragraphs provide a description of tire components drat comprise fiber optics of the security system.

The “Fiber Defender 205”, manufactured by Fiber SenSys, Inc (FSI), is part of a new generation of fiber-optic intrusion detection systems. They build on the fiber-optie intrusion detection technology developed by FSI and proven in the field over several years. Advanced signal processing benefits the customer with simplified setup and mainicnance and the lowest potcniio! nuisance alarm rate of any system.

VIKONICS, INC IIU3W-2 RIA'11 NwcmlKiy. I*«

NYC-WTC_000171946

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000171946Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Security system specification excerpt, May 1998 · Box 7DCAS

NYC-WTC_000173219

Technical specification document detailing end-of-line resistor wiring requirements for the Mayor's Office of Emergency Management security system.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.929

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

Fire Service Summary Report, n.d. · Box FDNY

NYC-WTC_000169205

Document summarizing fire service activities or inspections performed at the specified location.

Similar document embedding; no shared entity or topic indexed. · similarity 0.893

machine-extracted · confidence unavailable · Check page ↗

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →