Rider “C” ‘
General Requirements .
17. In the event the Conernecor’s work will affect the activation of ed actors, or other warning
devices, the Contractor shall request the WIC Construction | t have WIC Operations
maintenance personnel deactivate mich devices. During the jo: peried, tha contractor shall
provide qualified persannal to loek for sny Unsafe conditions and|conn :! the appropriate authorised
personnel to tule the necessary aovion, 9s directad by the WIG i 19 Jnapneney Upen termination
of above stated werk conditions, the Ceutnsetor shall request the TTC ‘Gastructien lagsueter and
WTC Operations maintenanes personnel te activae the smoke tog and aher warning devices
The Contract shall reinburse the Part Authority far the com of ing PTC Operations maintnends
personnel at the rate of d& 45.00 per hour (warmal time), ar $55.00 pa tour (preeijum time).
During burntag and welding operetions, the Cantractar must use amc 2 eater, Saucke egters are
available from the Port Authority at a rate of $25.00 per dey, per| unix.
|
Life Safety Systems i
18. a) The Tanant’s Consultant responsible for the praparacion of Contec! Jocuments aball provide
wiring diagrams, installation procedurw aad applicable Shop Draw | gs fur all new end existing
life safety systems to be modified. The drawings sball indicate! locat : ns of cable terminations,
sequence of operation, and specificacions of all the wemponent pars All cha life safety systems
shall be connected ta the World Trades Center Multiplex Syrtem. Sys mg involving more than one
floar ahall give a floor by floar firs indication to the Muhiplex Syste |. The applicable systam
shell include, but not be limited to, smoke detaction, pre-action cyst :ms, and Halon. The
documents required herein shall be submittad for Port Authority ren | ra at the time that other
required Tenans Alteration Application documents are submi
b) The Convector chall perform preliminary testing of all fire and life | fety equipment and systems
te ensure thet each component of every system functiond in ac we with the approved
Contract Documents, including bur not limiwd co all wiring ard cor : actianz, flow alarms, wamuper
alarms, electrical controls, emoke detectors, automatic dampers, int lock devices, sir testing of
piping, and other testing, a5 directed by the Port Authority. Aq app! : ved substitute for Halon,
a.g., air carbon diazide, or other inert gas, or 0 suitable Frean pay |: weed as a test medium
during the preliminary testiog of a Halon installation. All prelimina ; and final mcting shall bs
performed in the presmace of sub-conrraster’s pertounel acd Port A: i aecity staff, as rectileed by
the WTC Construction Supervising Engines. |
¢) Any fire safesy work, including hut nat limited to, smoke de ) | tinklers, Halon syswma,
‘ete., shall be completed and operational priur to the Tenant 1 the premises. Occupancy
may be parmitted prior ta completion of such work, anly if approve by the Port Authority, in
writing. In such instances, the Tengut most mainuiin a Gre weteb of the premises duving the time
that the promisas remains unatteaded, |
d) The Contractor ahall not perform any construction, hook-up, demo on, atc, at any location
other than within the physical boundaries ef he construction size as jiown on the Coatract
Drawings appended to the Teuant Alteratina Application. Fur any w ick not specifically chown
and noted on the approved Contract Drawings and which is outaide :! the eanmcrucdon site, and
the scope of which is part of the spproved Tenant Alteration Applic : jan, the contractor shall
submit te the WTC Supervising Enginess named harein before|the « ; ct routing to be followed ia
the performance af the Work. The routing shall then be evaluated b- the WTC Asbestos Contanl
Section to determine if any asbestos is present and if it might be dis; rbed.