← Document results/7DCAS/Attachment B - List of Comments 7 World Trade Center MOEM Swanke Hayden Connell Architects - Pit-Out of Space T.A.A. - 987134 Conceptual Review Submission 1
Document / 2 pages

Attachment B: Comments on fuel oil tank room, WTC

Machine-extracted title · confidence 95%

Attachment B listing Mayor's Office of Emergency Management comments on fire separation and structural adequacy for a new fuel oil tank.

NYC-WTC_000167723–000167724

Folder label: “Attachment B - List of Comments 7 World Trade Center MOEM Swanke Hayden Connell Architects - Pit-Out of Space T.A.A. - 987134 Conceptual Review Submission 1

Page image
Scanned page image, NYC-WTC_000167723
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

. JHN-03-iy00 Ori; 18 p.aj

A’CTACHMENT B “ LIST OF COMM}>;NTS 7 WORLD TRADE CENTER MAYOR'Si OFFICE OB' EMERGENCY MANAGEMENT SWANKE HAYbKN' CONNELL ARCHITECTS- E'.[T-(^T OF SPACE T.A.A. - 987134 CONCEPTUAL REVIEW SUBMISSION 1

! i

MCHITSC^ i (

1. Since the fuel olli tank room has an Occupejtocy Classification of "A," High Hara rd, a tour hour fire divisidn is required on all sides (including th® horizontal surfaces) . ‘Sec Code Section 214. 27-340, and Tablo 5!-?..

a. Drawing A-1-1. Please investigate the exist Ing Structure for its adequacy to support) the load of the new fuel oil storage tank. MHOiAliKAL i 3. Please indicate the size of the tank and .he material the tank will be construct^ of, Since the tank i.s located above the lowest floor, and above the existing storage room, only 275 gallons tanks wi ll I be permitted as per NYC Building Code .Section 27-8a9(b). Above .ground tanks larger chan 275 gallons must be located on the lowest floor and comply with provisions of Code) Section 27-289 {a}.! Show details on fill pipe and air ventiny pipe. ! 4. Drawing A-1-1. !/hi opace shall be ventilated as required by Code Section 27-405, high hazard occupancy, EtRS«£gfiTBCTION i ! I ■ ! s. Drawing A-i-i. Provide extra hazard sprinkler protection tor the tank room, as the space ia classified "high hazard,* see Comment i above. i 6. Provide detail i ufrormaclon on ”o Ll proof nuemferaae". 7. Provide informatiod on liquid alarms for detection of leaks. a. Provide infoxm\tIon on fire alarms.

3/11/98

C0’a sgaa wd6S:g hh^i ‘gi ?jbw Bt^sEsgggtgx :0i xbd roiNO’XJWoad NYC-WTC_000167723

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000167723Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

RFI log cover sheet, Sep 1998 · Box 7DCAS

NYC-WTC_000166743

Cover sheet for the Request for Information log documenting 37 received RFI items for the 7 World Trade Center project as of September 16, 1998.

Same agency, volume and box · similarity 0.922

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000169177 · Box FDNY

Battalion memo outlining fire protection concerns regarding a new 6000-gallon diesel storage system installation.

Similar indexed content

RFI log cover sheet, Sep 1998 · Box 7DCAS

NYC-WTC_000166743

Cover sheet for the Request for Information log documenting 37 received RFI items for the 7 World Trade Center project as of September 16, 1998.

Similar indexed content

Compare copies and versions →