NYC 9/11 Public Portal Document
5?
WKP mH
LABORATORIES, INC
AIR SAMPLE analysis REPORT
PHASE CONTRAST MICROSCOPY
CLIENT; WARREN & PANZER ENGINEERS, P.C. TURNAROUND TIME I4HRS
WKP PILE # 801-01 samRle date t'24/02
WKP LOG I.D, # N0204207, N020420a, and N0204209 received date 4^4/02
Contract K; WTC AR2 ANALYS16 OATS 4/26/02
REPORT DATE 4Z2S,'O2
CLIENT JOB: NYC Department ot Environmental Protection
CLIENT JOB #; 1079.01,01
LOCATION S.W. Area/ Site Map
ANALYSIS: airborne fiber counting, phase CONTRAST MICROSCOPY, NIOSH 7400, NIOSH PAT Lab NO, 07186; NY
COLteCTlON DEVICE: 25 mm MCE Filter Cassette; Collection Area = 365 sq mm;
SAMPLE WERE COLLECTED BY; Benny GiamUnone, J. Garcia, end Fesly Ocamv/egie
SUMMARY OF ANALYSIS
CLIENT FIBERS/ fibers/
SAMPLE# Site# SAMPLE LOCATION . Vol. sq mm ec
Gateway Plaza Park Area 675 0,00 <0.004
1079.01.01 001 27
South End Ave. and Albany Street 675 0.00 <0,004
002 31
W«4t Street and Albany Place 675 3.80 <0.004
003 32
Rector Place by the Park Place 675 0.00 <0.004
004 33A
34 W. Thames Street • Along Waterfront 675 0.00 <0.004
005
37 West ot Third Place 675 1.30 <0.004
006
West Street and Warren Street 675 6,40 0.004
007 8
4 River Terrace and Chambers Street 675 2.60 <0.004
008
6A River Terrace Park Ares Between Park Place and Warren Street 675 1.30 <0.004
009
River Terrace a.nd Park Place West 675 0,00 ■ <0.004
010 9
River Terrace and Vesey 675 1.30 <0.004
oil IT
Warren Street end North End Avenue 675 0.00 <0.004
012 7
North End Avenue Park place West .675 3.80 <0.004
013 10
Trinity Place and Thames Street 676 0.00 <0.004
014 29
Fulton and Church Street 676 0.00 <0.004
. 015 21
Vesey Street and West Broadway 675 0,00 <0.004
016 20A
Park place and Church Street 675 2,50 <0.004
017 16
Murray Street and Church Street 675 3,20 <0.004
018 12
Pailr Place and Greenwich Street 675 1.30 <0,004
019 15
Murray Street and Greenwich -Street 67S 2.50 <0,004
020 11
021 Field Blank 0.00
022 Field Blank 0.00
NOTES: 1, 5,5 FbersJ'OD fields was used to calculate the limit cf detection (LOO). Results below the LOD have no statistical validity,
2. Samples were not collected by WKP Laboratories, Ino.
3. The Federal EPA Clearance Critical following an asbestos abatement project is 0.010 fibers/cc.
4. PCM air samples will be disposed of after 3 months unless otherwise directed by client in writing.
Louis Lombardi
laboratory analyst laboratory director
NYC-WTC_000161799