. • Draft2 Comments by Covino Environmental Associates. Inc,
January 6.2003
7. Cover all open supply air grilles, supply diffusers, and return air grilles located in the
affected ductwork using fire-retardant polyethylene sheeting or bags and duct tape.
3-Vertical risers will be-treated similarly to the procedures identified-for exhaust ducts.
4;Look out-end tag out-the fan unit. I
^rS.Prepare-the unit to be cleaned. Outdoor fan units or units in non occupied areas require
minimal prep. Fan ^HHts located in occupied areas or-common areas used by tenants will
require-more extensive prep including isolating the work area, using negative pressure-or
local exhaust ventilation m appropriate, plasticize the horizontal surfaces below the-unit
if it is above greund. (Place the air handling units and their components under
)< containment prior to beginning work.^jA temporary Zip-wall containment of 6-mil. fire
retardant polyethylene sheeting extending from the floor to the ceiling deck, and
maintained under negative pressure using a HEPA-filtered air filtration device is
sufficient. The footprint of the containment should be large enough to accommodate a
ladder or scaffolding if needed^
9. If there is an outside air intake, clean the intake louvers by damp wiping. If there is an
outside air duct and it is accessible, clean the interior surfaces using HEPA vacuums with
brush attachments and wet methods. If access to the outside air duct is limited, clean it
using a combination of whips (whips only used in ducts without interior insulationl
brushes (use soft brushes if ducts have interior insulation), and compressed air (note:
compressed air may be used only if the system is sufficiently isolated and vacuum
collection equipment is used to maintain a duct velocity of approximately 3^ feet per
minute). Note that vertical risers may be treated similarly to the procedures identified for
exhaust ducts.
10. Clean the air intake louvers and filter racks at the return air sides of the AC/ventilation
units by damp wiping.
11. Clean all accessible-parts of the a/eA/C or ventilation fan unit exposed to the air stream
including thermal coils, the blower assembly and housing, and all other components
using HEPA vacuum brush attachments and minimal wet methods.- Electric coils and
components shall be cleaned using dry methods. When wet cleaning thermal coils, apply
manufacturer-approved cleaning solution to the coils using low pressure methods (i.e..
airless sprayer, hand operated pump), until all suspect WTC dust is removed.
12. Clean all supply mains and branch ducts in the direction of air flow, starting from the
furthest point from the AFP or vacuum collection device. If the ducts are accessible
(typically 6’ or less in length from access point) they may be cleaned using HEPA
vacuums with brush attachments and wet methods. If access to the ducts is limited, clean
them using a combination of whips (whips only used in ducts without interior insulation).
brushes (use soft brushes if ducts have interior insulation), and compressed air (note:
compressed air may be used only if the system is sufficiently isolated and vacuum
collection equipment is used to maintain a duct velocity of approximately 3000 feet per
minute).