c. At steel stud partitions, attach wall anchors to studs with tapping screws.
Spot grout anchors with USG Durabond Joint Compound just before
board is inserted Into frame; coordinate with Section 09250.
•
d. Place frames at fire-rated openings in accordance with NFPA Standard
No. 80.
e. Make field splices in frames as detailed on final shop drawings, welded
and finished to match factory work.
f. Remove spreader bars only after frames or bucks have been properly set
and secured.
4. Door Installation: Fit hollow metal doors accurately in their respective frames,
with the following clearances:
a. Jambs and Heads: 3/32".
b. Bottom: 1/4", where no threshold or carpet.
c. Place fire-rated doors with clearances as specified in NFPA Standard No.
80.
S. Wood Doors
1. Condition doors to average prevailing humidity in Installation area prior to
hanging.
2. Install doors in accordance with Manufacturer's instructions.
3. Fit doors to frames and machine for hardware to whatever extent not previously
worked at factory as required for proper fit and uniform clearance at each edge.
[I
4. Clearances: For non-fire doors provide clearances of: 1/8" at jambs and heads;
1/8" at meeting stills for pairs of doors; and 1/2" from bottom of door to top of
decorative floor finish or covering, except where threshold is shown or scheduled
provide 1/4" clearance from bottom of door to top of threshold.
5. Fire-Rated Doors: Install in corresponding fire-rated frames in accordance with
the requirements of NFPA No. 80. Provide clearances compliant with the
limitations of the authority having jurisdiction.
C. Adjustments: Check and readjust operating finish hardware items just prior to
final inspection. Leave work in complete and proper operating condition. Remove
and replace defective work, including doors or frames which are warped, bowed
or otherwise unacceptable.
3.04 BLOCKING AND MISCELLANEOUS WOOD
A. General:
1. Erect rough carpentry true to line, levels and dimensions required; squared,
aligned, plumbed, and securely fastened in place.
•