130 Cedar Street July 15, 2004
Carpentry
C. Bolts: Standard mild steel, square head machine bolts with square nuts and malleable
iron or steel plate washers or carriage bolts with square nuts and cut washers conforming
to the following:
1. Bolts: FS-FF-B-575 and 584.
2. Nuts: FF-N-836D.
3. Expansion Shields: FS-FF-B-561.
4. Toggle Bolts: FS-FF-B-561.
5. Lag Screws and Botts:_ FS-FF-B-561.
D. Wood Screws: Per Fed. Spec. FF-S-111 D.
E. Concrete and Masonry Anchors: Standard expansion shield self-drilling type concrete
anchors where so shown or noted on the drawings, or where approved by Architect.
PART 3.00 - EXECUTION
3.01 INSPECTION
A. Examine the areas and conditions where carpentry is to be installed and notify the
Architect of conditions detrimental to the proper and timely completion of the work. Do
not proceed with the work until unsatisfactory conditions are corrected to permit proper
installation of the work.
3.02 INSTALLATION OF FINISH HARDWARE
A. All finishing hardware specified In Section 08700 of this specification entitled "Door
Hardware" shall be received, accounted for, stored and applied under this Section.
B. Hardware shall be sorted and stored in space assigned by Contractor and shall be kept at
all times under lock and key. The safety and preservation of all items delivered will be the
responsibility of the Contractor.
C. Hardware shall be carefully fitted and securely attached, in accordance with these
specification and the Instructions of the various manufacturers.
D. Unless otherwise noted, mount hardware units at heights established in Section 08100.
E. Install each hardware item in compliance with Manufacturer's Instructions and
recommendations. Wherever cutting and fitting Is required to install hardware onto or Into
surfaces which are later to be painted or finished in another way, install each item
completely and then remove and store In a secure place during the finish application.
After completion of the finishes, re-install each Item. Do not install surface-mounted items
until finishes have been completed on the substrate.
F. Set units level, plumb and true to line and location. Adjust and reinforce the attachment
substrate as necessary for proper Installation and operation.
G. Drill and countersink units which are not factory prepared for anchorage fasteners. Space
fasteners and anchors In accordance with industry standards.
06200-4
NYC-WTC 000125194