structure concentration per square centimeter of surface area (s/cm2). The publication
"Advances in Environmental Measurement Methods for Asbestos" prepared by the ASTM
Committee D-22 on Sampling Analysis of "Atmospheres in conjunction with the Environmental
Information Association references the following guidelines pertaining to asbestos in surface
dust.
<1,000 s/cm2 indicates low level
>10,000 s/cm2 indicates above general background level
>100,000 s/cm2 indicates high level
Laboratory analysis found no asbestos fibers present in 14 of the 16 samples collected.
Chrysotile was detected in 2 samples, however results indicate low level concentrations below
the stated "low level" criteria of 1,000 s/cm2. Analytical results are shown below in Table 2.
Table 2 Asbestos in Dust SamnlinR
Sample No. Location Results — Asbestos Concentration
North Building
MV-01 7th Floor Room N733 None detected
MV-03 5th Floor Hallway by Room N516 None detected
MV-05 3`d Floor Lobby by Room N306 None detected
MV-07 1' Floor Hallway by Room Ni 18C <851.899str/cm2 - Chrysotile
South Building
MV-02 7th Floor Room S757 None detected
MV-04 5th Floor Media Center Room S506 None detected
MV-06 3 Floor Corridor by Room S332 None detected
MV-08 3Td Floor Lobby by Room Si l0H None detected
Trailers
MV-09 Harrison Street Trailer #H103 None detected
MV-10 Trailer #W102 None detected
MV-11 Trailer #Wl05 None detected
MV-12 Trailer #Wl 09 None detected
MV-13 Trailer #W112 None detected
MV-14 Trailer #W107 <340.760str/cm2 - Chrysotile
MV-15 Harrison St. Trailer #H101 None detected
MV-16 Trailer #W103 None detected
Lead Surface Sampling
PSI collected 8 representative surface wipe samples from alternate floors from within the North
and South Buildings and 8 representative air samples from each of eight of the Trailers on
January 31g, 2001. Surface wipe samples were analyzed by EPA Method SW846-7420.
Results indicate all sample concentrations are below the EPA Leaded Dust Level Criteria of 40
micrograms per square foot for floor surfaces. The analytical results of lead surface testing are
summarized in Table 3 below.