i . I Quantitation Report (QT Reviewed)

Data File : C:\HPCHEM\1\DATA\010CT09\1009R40.D Vial: 3 Acq On 9 Oct 2001 12:10 pm Operator: Sample : ref 40 Inst : GC/MS Ins Misc Multiplr: 1.00 MS Integration Params: LSCINT.P Quant Time: Oct 10 14:41 2001 Quant Results File: HP092601.RES

Quant Method : C:\HPCHEM\1\METHODS\HP092601.M (RTE Integrator) Title : VOCs BY EPA METHOD 524 Last Update : Wed Sep 26 08:36:04 2001 Response via : Initial Calibration DataAcq Meth : HP092601

Compound R.T. Qlon Response Conc Unit Qvalue ------------------------------------------------------------------------- 34) CIS-1,3-DICHLOROPROPENE 17.08 75 3579419 39.43 ug/L 99 35) TOLUENE 17.83 91 12336628 44.52 ug/L 98 36) TRANS-1,3-DICHLOROPROPENE 18.10 75 2448584 40.15 ug/L 97 37) 1,1,2-TRICHLOROETHANE 18.49 97 1258213 36.92 ug/L 99 38) TETRACHLOROETHENE 19.26 166 2508196 37.05 ug/L 99 39) 1,3-DICHLOROPROPANE 19.01 76 2626431 41.24 ug/L 98 40) DIBROMOCHLOROMETHANE 19.69 129 1444253 36.59 ug/L 100 41) 1,2-DIBROMOETHANE 20.13 107 1114147 35.60 ug/L 99 42) CHLOROBENZENE 21.02 112 7001964 39.43 ug/L 96 43) 1,1,1,2-TETRACHLOROETHANE 21.07 131 1995959 37.02 ug/L 100 44) 2-HEXANONE 18.39 43 730075 59.65 ug/L 99 45) ETHYLBENZENE 21.07 91 14117746 43.09 ug/L 98 46) P & M-XYLENE 21.22 106 10428581 85.80 ug/L 94 47) O-XYLENE 22.19 91 10808276 42.44 ug/L 98 48) STYRENE 22.24 104 7870190 40.64 ug/L 95 49) 1,1,2,2-TETRACHLOROETHANE 23.26 83 1274684 36.22 ug/L 100 51) BROMOFORM 23.08 173 616934 35.76 ug/L 99 52) ISOPROPYLBENZENE 22.91 105 13177162 48.29 ug/L 97 53) 1,2,3-TRICHLOROPROPANE 23.59 110 321247 38.72 ug/L 88 54) N-PROPYLBENZENE 23.78 91 17795669 48.41 ug/L 97 55) BROMOBENZENE 24.00 156 2278944 37.38 ug/L 82 56) 1,3,5-TRIMETHYLBENZENE 24.10 105 11165727 47.28 ug/L 98 57) 2-CHLOROTOLUENE 24.25 91 9988265 50.05 ug/L 98 58) 4-CHLOROTOLUENE 24.32 91 9115600 44.55 ug/L 94 59) TERT-BUTYLBENZENE 24.88 134 2294066 43.75 ug/L 96 60) 1,2,4-TRIMETHYLBENZENE 24.99 105 11593084 47.15 ug/L 98 61) SEC-BUTYLBENZENE 25.34 105 15393424 47.44 ug/L 99 62) P-ISOPROPYLTOLUENE 25.60 119 12261329 45.35 ug/L 99 63) 1,3-DICHLOROBENZENE 25.94 146 5048474 38.00 ug/L 98 64) 1,4-DICHLOROBENZENE 26.16 146 4976613 37.87 ug/L 100 65) N-BUTYLBENZENE 26.48 91 13281213 49.69 ug/L 98 66) 1,2-DICHLOROBENZENE 27.00 146 4022372 37.03 ug/L 98 67) 1,2-DIBROMO-3-CHLOROPROPAN 28.65 157 152085 30.54 ug/L 99 68) NITROBENZENE 28.84 77 1023511 896.09 ug/L 92 69) 1,2,4-TRICHLOROBENZENE 30.57 180 2009558 28.47 ug/L 98 70) HEXACHLOROBUTADIENE 30.81 225 1020702m 21.08 ug/L 71) NAPHTHALENE 31.24 128 3411134m 42.97 ug/L 72) 1,2,3-TRICHLOROBENZENE 30.57 180 1999659m 38.94 ug/L

------------------------------------------------------------------------- (#) = qualifier out of range (m) = manual integration 1009R40.D HP092601.M Tue Nov 13 10:36:53 2001 Page 2

NYC-WTC 000000778

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000000778Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

WTC sample cover sheet, Nov 27 2001 · Box DEP Box 04

NYC-WTC_000001851

Cover page for environmental sample records from November 27, 2001, associated with the World Trade Center site.

6 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.989

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →