Ventilation, Air Monitoring and Thermal comfort

The area is served by four air conditioning/ventilation (AC) units located on the same floor. It is a constant volume AC/ventilation system. The mechanical room was found to be in a good condition, with the pleated air filters in good shape. The units were in operation, and outside air dampers were open. Ventilation to the offices is provided through ducts and ceiling vents. All vents were functioning (see attached technical report). The outdoor air intake is located on the roof. According to Mr. Faust, the perimeter heating unit output can be adjusted. However, there are no thermostats to control supply air temperature to the interior spaces.

We conducted measurements of carbon dioxide, carbon monoxide, formaldehyde, ozone, temperature and relative humidity. Carbon dioxide levels were 450-525 ppm, below the upper limit of 1,000 ppm recommended by ASHRAE thus indicating adequate ventilation. Carbon monoxide levels were 0-1 ppm, much lower the OSHA standard. Formaldehyde and ozone were not detected.

Temperatures in the offices were in range of 75-77.5°F. The American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) recommends that temperatures be maintained between 68.5 and 76°F in the winter season. Overheating of offices raises the dryness of air, creates uncomfortable thermal conditions and increases energy consumption. According to EPA/NIOSH publication Building Air Quality, a Guide for Facility Managers (p.57) recent research suggests that lAQ is judged to be worse as temperatures rise above 76"F, regardless of the actual air quality.

Relative humidity (RH) was low, in 10.5-12.1% range, below ASHRAE minimum recommended level of 30%. It should be noted that in winter RH indoors often drops below 20%, since the outside RH is also low. If temperatures are maintained at the lower end of the comfort range (70- 72°F) during heating periods, the RH will not fall much below 20%. RH levels below 20% are associated with increased discomfort, drying of the mucous membranes, eye irritation and the frequency of colds. Dry air also fosters the breaking of fibers in carpets and other fabrics.

General housekeeping in the work area was adequate. At the conclusion of the survey, 1 discussed my findings and recommendations with Susan Hart and yourself.

Recommendations:

COSH recommends the following to improve the safety and health aspects of the work environment:

• Maintain space air temperatures at the lower end of the comfort range (70-72°F) during heating periods, thus increasing indoor relative humidity.

• Install additional HVAC controls in order to be able to adjust temperature within the interior space.

A technical report and Appendix A (Information on indoor air quality) is attached. Please

CITY_21MC100_006268778

NYC-WTC_000456034

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000456034Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality survey memo, Aug 2000

NYC-WTC_000234727

Memorandum detailing an indoor air quality survey conducted at a city building in response to employee concerns about air conditions.

Similar indexed content

Compare copies and versions →