machine-extracted · confidence unavailable · Check page ↗Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
NYC-WTC_000455806–000455811OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
symptoms that employees currently have are consistent with flu season. According to Department of Health, this year it goes from beginning of October to mid-April.
Ventilation, Air Monitoring and Thermal comfort
We were requested to check rooms 208 and 210 as areas from where complaints originated. For comparison we conducted air monitoring in similar rooms 205 and 315. All these rooms have a high ceiling, approximately 20 feet. Generally, higher ceilings contribute positively to indoor air quality.
When the building was renovated two years ago new air handling units (AHU) and ducts were installed. Rooms 208, 210, 205 and 315 are served by a constant volume ventilation system. All AHUs are controlled automatically, with area temperatures and other parameters being set from the computer located in the basement. The units have two stage air filtration: pleated type medium efficiency filters and bag type high efficiency air filters. The level of air filtration far exceeds those recommended by EPA/ NIOSH (see the list of acronyms at the end of the report). The cooling coils were clean, and no rust under the coils was observed. No standing water or slime which might promote growth of microorganisms and boost allergic reactions was found.
The outdoor air intake is located on the roof. Ventilation and heating to the floors is provided through ducts and wall vents located near the ceiling. Return vents are located about two feet above the floor. There is no thermal insulation inside the ductwork; all ducts are thermally insulated on the exterior.
Carbon monoxide levels measured were in the range of 0 to 1 parts per million (ppm), which is well below both the PESH PEL and NAAQS of 35 ppm and 9 ppm accordingly. Volatile organic compounds were not detected. Carbon dioxide (CO2) levels were in the range of 675- 825 parts per million, below the ASHRAE recommended maximum of 1,000 ppm (ASHRAE Standard 62-1989 “Ventilation for Acceptable Indoor Air Quality”.) CO2 levels below 1,000 ppm are an indicator of adequate ventilation rate. Since carbon dioxide is given off by humans when exhaling, its level in the air provides an indication on how effective the ventilation system is in diluting and removing contaminants from the air. All air vents were in operation.
The temperature on the day of the survey was in the range of 72-77° F, within the ASHRAE guidelines. Relative humidity was in range of 9-11 %, below ASHRAE recommended guidelines. It should be noted that in winter RH often drops below 20%, since the outside RH is also low. RH levels below 20% are associated with increased discomfort and drying of the mucous membranes.
A technical report and Appendix A (discussion on factors affecting indoor air quality) is attached. Please contact me at (212) 669-8852, if you have any questions.
CITY_21MC100_006268800
NYC-WTC_000455807
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000456033
Cos Health/COSH memo on IQA survey at 100 [name] building following complaints.
7 shared non-person entities · 1 shared topics · similarity 0.978
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000234853
Memorandum detailing an indoor air quality survey and dust monitoring conducted in response to employee respiratory concerns.
8 shared non-person entities · 1 shared topics · similarity 0.963
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000454439
COSH-drafted memo describing indoor air quality survey and sampling in City offices.
8 shared non-person entities · 1 shared topics · similarity 0.963
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
3 shared non-person entities · 1 shared topics · similarity 0.958
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255821
ATC memo with IAQ measurements at Stuyvesant High School.
3 shared non-person entities · 1 shared topics · similarity 0.956
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401790
ATC reports IAQ measurements taken January 11, 2002 at Stuyvesant High School.
3 shared non-person entities · 1 shared topics · similarity 0.956
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311250
ATC report of IAQ measurements at Stuyvesant High School.
3 shared non-person entities · 1 shared topics · similarity 0.956
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236945
Report of indoor air quality measurements collected on January 24, 2002, at P.S. 89M.
3 shared non-person entities · 1 shared topics · similarity 0.955
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236977
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
3 shared non-person entities · 1 shared topics · similarity 0.955
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236967
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
3 shared non-person entities · 1 shared topics · similarity 0.955
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274045
December 20, 2001 IAQ measurements at Stuyvesant High School for BOE.
3 shared non-person entities · 1 shared topics · similarity 0.955
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236953
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
3 shared non-person entities · 1 shared topics · similarity 0.954
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000456033
Cos Health/COSH memo on IQA survey at 100 [name] building following complaints.
Similarity score 0.971 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000234853
Memorandum detailing an indoor air quality survey and dust monitoring conducted in response to employee respiratory concerns.
Similarity score 0.957 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000454439
COSH-drafted memo describing indoor air quality survey and sampling in City offices.
Similarity score 0.956 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219378
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
Similarity score 0.951 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000329970
Report of IAQ assessment for Technology at PS 2M.
Similarity score 0.951 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401773
Indoor air quality measurements report for Stuyvesant High School dated January 10, 2002.
Similarity score 0.951 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000456033
Cos Health/COSH memo on IQA survey at 100 [name] building following complaints.
Similar indexed content
NYC-WTC_000234853
Memorandum detailing an indoor air quality survey and dust monitoring conducted in response to employee respiratory concerns.
Similar indexed content
NYC-WTC_000454439
COSH-drafted memo describing indoor air quality survey and sampling in City offices.
Similar indexed content
NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
Similar indexed content
NYC-WTC_000255821
ATC memo with IAQ measurements at Stuyvesant High School.
Similar indexed content