Quality IQ survey, 52 Chambers Street, Mar 2003

Machine-extracted title · confidence 36%

Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.

NYC-WTC_000455806–000455811
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

symptoms that employees currently have are consistent with flu season. According to Department of Health, this year it goes from beginning of October to mid-April.

Ventilation, Air Monitoring and Thermal comfort

We were requested to check rooms 208 and 210 as areas from where complaints originated. For comparison we conducted air monitoring in similar rooms 205 and 315. All these rooms have a high ceiling, approximately 20 feet. Generally, higher ceilings contribute positively to indoor air quality.

When the building was renovated two years ago new air handling units (AHU) and ducts were installed. Rooms 208, 210, 205 and 315 are served by a constant volume ventilation system. All AHUs are controlled automatically, with area temperatures and other parameters being set from the computer located in the basement. The units have two stage air filtration: pleated type medium efficiency filters and bag type high efficiency air filters. The level of air filtration far exceeds those recommended by EPA/ NIOSH (see the list of acronyms at the end of the report). The cooling coils were clean, and no rust under the coils was observed. No standing water or slime which might promote growth of microorganisms and boost allergic reactions was found.

The outdoor air intake is located on the roof. Ventilation and heating to the floors is provided through ducts and wall vents located near the ceiling. Return vents are located about two feet above the floor. There is no thermal insulation inside the ductwork; all ducts are thermally insulated on the exterior.

Carbon monoxide levels measured were in the range of 0 to 1 parts per million (ppm), which is well below both the PESH PEL and NAAQS of 35 ppm and 9 ppm accordingly. Volatile organic compounds were not detected. Carbon dioxide (CO2) levels were in the range of 675- 825 parts per million, below the ASHRAE recommended maximum of 1,000 ppm (ASHRAE Standard 62-1989 “Ventilation for Acceptable Indoor Air Quality”.) CO2 levels below 1,000 ppm are an indicator of adequate ventilation rate. Since carbon dioxide is given off by humans when exhaling, its level in the air provides an indication on how effective the ventilation system is in diluting and removing contaminants from the air. All air vents were in operation.

The temperature on the day of the survey was in the range of 72-77° F, within the ASHRAE guidelines. Relative humidity was in range of 9-11 %, below ASHRAE recommended guidelines. It should be noted that in winter RH often drops below 20%, since the outside RH is also low. RH levels below 20% are associated with increased discomfort and drying of the mucous membranes.

A technical report and Appendix A (discussion on factors affecting indoor air quality) is attached. Please contact me at (212) 669-8852, if you have any questions.

CITY_21MC100_006268800

NYC-WTC_000455807

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000455807Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →