(TVOCs) and respirable particulates (PM2.5) were also measured. ATC’s findings are
based on a visual inspection, real-time environmental measurements and conditions
present in the school at the time of the assessment. ATC measured temperature,
relative humidity, CO2 and CO with a Q-Trak Model 8551. ATC measured
concentrations of respirable particulates (PM2.5) with a Dust-Trak Aerosal Monitor
Model 8520. ATC measured concentrations of TVOCs using a photionization
detector (PID). The assessment was conducted consistent with generally accepted
indoor air quality assessment practices. Currently, there are no regulatory standards
for indoor air quality in non-industrial buildings. For the real-time data collected,
ATC used commonly accepted guidelines from industry publications. ATC used the
commonly accepted guidelines from industry publications. In the January 15, 2002
report, concentrations of respirable particulates, CO2, CO and TVOCs were within
applicable standards and guidelines. All indoor measurements of relative humidity
were below the recoimnended range of 30 to 60 percent for occupant comfort. Seven
temperature measurements were above the recommended range of 68 to 75° F at 50
percent relative humidity during wintertime conditions. In the January 16, 2002
report, measurements of temperature, relative humidity and concentrations of
respirable particulates, CO2, CO and TVOCs were within applicable standards and
guidelines. In the January 17, 2002 report, concentrations of respirable particulates,
CO2, CO and TVOCs were within applicable standards and guidelines. All Indoor
measurements of relative humidity were below the recommended range of 30 to 60
percent for occupant comfort. Nineteen temperature measurements were above the
recommended range of 68 to 75° F at 50 percent relative humidity during wintertime
conditions. In the January 18, 2002 report, concentrations of respirable particulates,
CO2, CO and TVOCs were within applicable standards and guidelines. One indoor
measurements of relative humidity was within the recommended range of 30 to 60
percent for occupant comfort. All other measurements were below the ASHRAE-
recommended range. Three temperature measurements were above and four were
below the recommended range of 68 to 75° F at 50 percent relative humidity during
wintertime conditions. In the January 19, 2002 report, concentrations of respirable
particulates, CO2, CO and TVOCs were within applicable standards and guidelines.
Indoor measurements of relative humidity were below the recommended range of 30
to 60 percent for occupant comfort. Six temperature measurements were below and
one was above (misstated) the recommended range of 68 to 75° F at 50 percent
relative humidity during wintertime conditions.
14. January 16, 17, 18, 19, 2002 indoor air quality assessment reports for P.S. 89M. The
evaluation assessed the basic parameters of temperature, relative humidity, carbon
dioxide (CO2) and carbon monoxide (CO).
15. In a letter dated January 12, 2002, ATC reported the results from the January 12,
2002 transmission electron analysis (TEM) of air samples from P.S. 89. In a letter
dated January 17, 2002, ATC reported the results from the January 17, 2002
transmission electron analysis (TEM) of air samples from P.S. 89. In a letter dated
January 18, 2002, ATC reported the results from the January 18, 2002 transmission
electron analysis (TEM) of air samples from P.S. 89. In a letter dated January 19,