Mr. Bernard P. Orlan April 12, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time envipionmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8.03 A.M. and concluded after 15:17 P.M. The results are described belov/.
Temper^ire
Indoor dry bulb temperature measurements ranged from 69.7 °F to 75.0 °F. All one hundred twenty eight (128) indoor measurements for temperature were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 55.7 °F to 64.2 °F.
Relative Humia'itv
The relative humidity indoors ranged from 27.9 percent to 35.8 percent. Twenty two (22) of the indoor measurements for relative humidity were below' and one hundred and six (106) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant cornfort. The outdoor relative humidity range was 29.5 to 41.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 431 ppm to 1344 ppm. One hundred and twenty four (124) readings of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 554 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1254 ppm (background level + 700 ppm). The highest level of CO2 1344 ppm was detected in room # 1015 with thirty one (31) occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupam: respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NTAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm- 3 ppm.
Respirable Particulates (PM2,j)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 18 pg/m^ with an average 9 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 20 pg/m3 to 43 pg/m3 with an average of 29 pg/m^. None of the outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hour average
CONFIDENTIAL, CITY_21MC100_003463894 SUBJECT TO PROTECTIVE ORDER NO, 2, SEPT. 2008
NYC-WTC_000260094
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000370492
Indoor air quality measurements collected March 12, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259999
IAQ field report for March 15, 2002 measurements
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260136
ATC IAQ measurements collected April 23, 2002 at the referenced school for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394813
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296816
ATC IAQ measurements report for 90 Trinity Place, Apr 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259977
IAQ measurements collected Mar 13, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259941
IAQ measurements collected Mar 11, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260100
ATC IAQ measurements collected April 15, 2002 at the referenced school for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260177
April 29, 2002; cover about IAQ measurements at the school.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259999
IAQ field report for March 15, 2002 measurements
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189316
Report on indoor air quality measurements collected at a school building to evaluate environmental conditions in March 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370492
Indoor air quality measurements collected March 12, 2002 at the referenced school.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements collected March 12, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
Similar indexed content
IAQ field report for March 15, 2002 measurements
Similar indexed content
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
Similar indexed content
NYC-WTC_000260136
ATC IAQ measurements collected April 23, 2002 at the referenced school for BOE.
Similar indexed content