Mr. Bernard P. Orlan March 18,2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Proiect No. 15-19125-0290 Real-Time E.nvironmental Measurements ATC collected, orc hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 12:40 A.M. and concluded after 2:58 P.M. The results are described below.
TemDerature
Indoor dry bulb temperature measurements ranged from 69.9 °F to 76.8 °F. Eighty-five (85) indoor measurement for temperature were within and forte -three (43) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 57.7 °F to 65.6 °F.
Relative Humidity
The relative humidity indoors ranged from 39.1 percent to 54.4 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 41 to 50.8 percent.
Carbon Dioxide Concentration
Carbon dioxide; concentrations indoors ranged from 452 ppm to 2603 ppm. Thirty-seven (37) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 462 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1162 ppm (background level -t- 700 ppm). The highest reading (2603 ppm) was measured in room 905 at 2;05 PM with 27 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm- 4 ppm.
Respirable Particulates (PM2,$)
Respirable parl:iculate concentrations* indoors ranged between 24 pg/m^ to 98 ug/m^ with an average 42 pg/m^- Ten (10) of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Fifty-two (52) of the one-hundred twenty-eight (128) instantaneous measurements were above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m3. The outdoor respirable particulate concentrations ranged from 100 pg/m^ to 183 pg/m^ with an average of 143 pg/m^. All of the outdoor measurements were above the NRYAt^S of 65 pg/m^ 24-hour average concentration of particulate matter 2.5
CONFIDENTIAL, CITY_21MC100_003463678 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260001
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259941
IAQ measurements collected Mar 11, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260028
ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259977
IAQ measurements collected Mar 13, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260092
ATC IAQ report for 90 Trinity Place, measurements collected April 11, 2002, BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370534
Indoor air quality measurements collected March 21, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260023
IAQ measurements collected Mar 19, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000409958
ATC report of IAQ measurements at High School for Leadership, March 2002, for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260060
ATC IAQ measurements at the referenced school, March 27, 2002, per BOE request.
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000260092
ATC IAQ report for 90 Trinity Place, measurements collected April 11, 2002, BOE program.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189316
Report on indoor air quality measurements collected at a school building to evaluate environmental conditions in March 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259941
IAQ measurements collected Mar 11, 2002 for BOE
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259977
IAQ measurements collected Mar 13, 2002 for BOE
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements collected Mar 11, 2002 for BOE
Similar indexed content
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000260028
ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.
Similar indexed content
IAQ measurements collected Mar 13, 2002 for BOE
Similar indexed content
NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
Similar indexed content