NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 18, 2002 Indoor Air Quality Assessment Page 2 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 The assessment W2.s performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALTATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and. schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET __________ I ■.i--ft/ft ■ J Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS)____________ Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m3) 24-hour average 40 pg/m- 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Enviroiunental Protection Agency NPAAQS National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC1OO_OO3463677 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260000
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259941
IAQ measurements collected Mar 11, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260028
ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259977
IAQ measurements collected Mar 13, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260092
ATC IAQ report for 90 Trinity Place, measurements collected April 11, 2002, BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370534
Indoor air quality measurements collected March 21, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260023
IAQ measurements collected Mar 19, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000409958
ATC report of IAQ measurements at High School for Leadership, March 2002, for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260060
ATC IAQ measurements at the referenced school, March 27, 2002, per BOE request.
12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370473
March 11, 2002 IAQ measurements report for the BOE school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214382
Letter transmitting indoor air quality measurement results collected at P.S. 150M on May 13, 2002, for pre-reoccupancy evaluation.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370440
Indoor air quality measurements collected March 7, 2002 at the referenced school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements collected Mar 11, 2002 for BOE
Similar indexed content
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000260028
ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.
Similar indexed content
IAQ measurements collected Mar 13, 2002 for BOE
Similar indexed content
NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
Similar indexed content