were analyzed by EPA Method 8270C. The sampling was performed consistent with
generally accepted industrial hygiene practices. Ten samples underwent analysis for
PCBs and ten samples for PAHs. Samples were taken from areas specified by the
parents association consultant. Each sample was analyzed for secen PCB compounds
and sixteen PAHs. The PCB and PAH results of all samples collected were below the
reporting limits of 2.0 and 5.0 micrograms/sample. The EPA spill clean-up standard
for PCBs on non-porous surfaces is 10 micrograms per 100 square centimeters or less
as stated in 40 CER 761. No regulatory standards have been established for PAHs on
surfaces. In a letter dated January 10, 2002, ATC reported the results from wipe
samples for dioxins collected on December 20, 2002 at P.S. 89M. The samples were
collected using gauze pads and hexane as a solvent which were provided by Pace
Analytical Services. The analysis was performed according to EPA Method 8290
using combined capillary column gas chromatography/high resolution mass
spectrometry. The sampling was performed consistent with generally accepted
industrial hygiene practices. Neither the EPA or OSHA have established a standard
for dioxin in surfaces. The EPA has a residential clean-up goal of 1 part per billion
(ppb). NYSDEC has set 0.0006 parts per million as the allowable concentration of
dioxin in soil. ATC submitted ten wipe samples plus one blank for PCDDs/PCDFs to
Pace for analysis. Samples were taken from areas specified by the parents association
consultant. Each sample was analyzed for sixteen PCDD/PCDE isomers. The results
for each isomer were then converted to 2, 3, 7, 8 -tetrachloro-dibenzo-p-dioxin
equivalents by multiplying by an established equivalency factor. The concentrations
on indoor surfaces ranged from 0.00 to 0.032 nanograms per square meter. No
standard has been established for dioxin in indoor surfaces. The EPA residential
clean-up goal is 1 ppb. The levels found in these samples would appear to be below
these levels. It is not possible to detect when the 2, 3, 7, 8 - TCDD equivalents
detected in these samples were deposited.
12. In a letter dated January 7, 2002, ATC reported the results from the particulate
monitoring filter comparison report for P.S. 89M. The samples were taken in four
classrooms and compared the concentration of particulate matter (PM2.5) with
different filters installed on the Uni-vents. January 17, 2002 bulk and scotch magic
tape sampling for asbestos report for P.S. 89M. Eleven samples were analyzed
utilizing PLM.
13. In a letter dated January 15, 2002, ATC reported the results from January 11, 2002
indoor air quality assessment measurements for P.S. 89M. In a letter dated January
16, 2002, ATC reported the results from the January 15, 2002 indoor air quality
assessment measurements for P.S. 89M. In a letter dated January 17, 2002, ATC
reported the results from the January 16, 2002 indoor air quality assessment
measurements for P.S. 89M. In a letter dated January 18, 2002, ATC reported the
results from the January 17, 2002 indoor air quality assessment measurements for P.S.
89M. In a letter dated January 19, 2002, ATC reported the results from the January
18, 2002 indoor air quality assessment measurements for P.S. 89M. ATC conducted
this evaluation to assess the basic parameters of temperature, relative humidity,
carbon dioxide (CO2) and carbon monoxide (CO). Total volatile organic compounds