Mr. Bernard P. Orlan February 28, 2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and FinaiicefMS^ ATC Project No. 15-19125-0291
TVOC Concent7-ation
TVOCs were not detected anyw'here inside the building (0.0 ppm). Tlie outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FEND INGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO, CO2 and TVOCs, were within applicable
standards and guidelines.
2. Twenty-two (22) temperature measurements were below the range of 68 to 75°F (at 50
percent relative humidity recommended by ASHRAE Standard 55-1992 during the heating
season (wintertime conditions).
3. Two (2) of the relative humidity measurements were within the ASHRAE recommended
range of 30 to 60 percent for occupant comfort. All other relative humidity measurements
were below the ASHRAE recommended range.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 01-212.
Sincerely, Reviewed by;
H rCASSOCIA TES INC.
L
agg
Andreas C. Andreou ■lames R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment