NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 28, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance CMSSjI ATC Project No. 15-19125-0291

Real-Time Environmental Measurements

ATC collected sixty-five (65) sets of real-time environmental measurements consisting of sixty- two (62) in the school building and three (3) outdoors. Field data sheets are found in the Attachment. Readings began at 3;08 P.M. and concluded after 6:00 P.M. The results are described below.

TemiKratirre

indoor dry bulb temperature measurements ranged from 61.4"F to 71.6°F. Twenty-two (22) of the measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 44.9 to 46.2°F.

Relalive Humidiry

The relative humidity indoors ranged from 20.3 percent to 39.1 percent. Only two (2) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the ASHRAE recommended range. The outdoor relative humidity ranged from 2! .0 to 21.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 274 ppm to 823 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COy concentration was 265 ppm. Therefore, the maximum acceptable level of COy at this location was 965 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COy indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1-3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 to 4 ppm.

Respirable Particulatex

Respirable particulate concentrations* indoors ranged between 3 pg/nH to 27 pg/m^ with an average 7 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The PM? 5 average concentration was also below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. Tlie outdoor respirable particulate concentration ranged from 17 pg/m^ to 35 pg/m^ .

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CONFIDENTIAL, CITY_21MC100_003463041 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259561

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259561Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000179968

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 1, 2002.

Similar indexed content

Compare copies and versions →