NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 28, 2002
Indoor Air Quality Assessment Page 3
H.S. of Economics and Finance CMSSjI ATC Project No. 15-19125-0291
Real-Time Environmental Measurements
ATC collected sixty-five (65) sets of real-time environmental measurements consisting of sixty-
two (62) in the school building and three (3) outdoors. Field data sheets are found in the
Attachment. Readings began at 3;08 P.M. and concluded after 6:00 P.M. The results are
described below.
TemiKratirre
indoor dry bulb temperature measurements ranged from 61.4"F to 71.6°F. Twenty-two (22) of
the measurements were below the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature ranged from 44.9 to 46.2°F.
Relalive Humidiry
The relative humidity indoors ranged from 20.3 percent to 39.1 percent. Only two (2)
measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. All other measurements were below the ASHRAE recommended range. The outdoor
relative humidity ranged from 2! .0 to 21.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 274 ppm to 823 ppm. All of the
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) COy
concentration was 265 ppm. Therefore, the maximum acceptable level of COy at this location
was 965 ppm (background level + 700 ppm). Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. The primary source of COy indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1-3 ppm. These concentrations were below the
NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 to 4 ppm.
Respirable Particulatex
Respirable particulate concentrations* indoors ranged between 3 pg/nH to 27 pg/m^ with an
average 7 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
The PM? 5 average concentration was also below the USEPA recommended concentration of 40
pg/m^ for sensitive individuals / children. Tlie outdoor respirable particulate concentration
ranged from 17 pg/m^ to 35 pg/m^ .
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.