Mr. Bernard P. Orlan May 21, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC ProjectNo. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
TemiJerature
Indoor dry bulb temperature measurements ranged from 64.2 °F to 75.1 °F. Thirty-six (36) of the indoor measurements for temperature was below and ninety-two (92) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 55.1 to 68°F.
Relative Humidity
The relative humidity indoors ranged from 23 percent to 42.1 percent. Seventy-one (71) of the indoor measurements for relative humidity were below and fifty-seven (57) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 19 to 27.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 577 ppm to 2861 ppm. Sixty-three (63) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 536 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1236 ppm (background level + 700 ppm). The highest reading (2810 ppm) was taken in room 905 at 2:16 PM with 23 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to 1 ppm.
Respirable Particulates (PM2_j)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 63 pg/m^ with an average 20 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the one hundred twenty-eight (128) instantaneous indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 21 pg/m^ to 76 pg/m^ with an average of 40 pg/m^.
CITY_21MC100_003079480
NYC-WTC_000291876
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000399420
Indoor air quality measurements collected May 20, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291705
Indoor air quality report for High School for Leadership & [name], May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399312
Indoor air quality measurements collected May 10, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291823
lAQ measurements report for HS Leadership, 90 Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394850
ATC IAQ report for High School for Leadership & [name], Trinity Place, April 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399254
Indoor air quality report dated May 7, 2002 for High School project; ATC.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291805
Report of lAQ measurements for HS Leadership at 90 Trinity Place, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291964
ATC report detailing IAQ measurements at High School for Leadership & [name], Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000399420
Indoor air quality measurements collected May 20, 2002, for the High School for Leadership & [name].
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260529
ATC IAQ measurements collected June 5, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291723
Indoor air quality measurements report for HS Leadership & [name], May 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399348
IAQ measurements collected May 14, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296893
Indoor air quality measurements at the referenced HS, BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291972
ATC IAQ measurements at the referenced school, June 3, 2002, per BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000399420
Indoor air quality measurements collected May 20, 2002, for the High School for Leadership & [name].
Similar indexed content
NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
Similar indexed content
Indoor air quality report for High School for Leadership & [name], May 2002.
Similar indexed content
NYC-WTC_000399312
Indoor air quality measurements collected May 10, 2002, for the High School for Leadership & [name].
Similar indexed content
NYC-WTC_000291823
lAQ measurements report for HS Leadership, 90 Trinity Place, May 2002.
Similar indexed content