Mr. Bernard P. Orlan May 8, 2002
Indoor Air Quality Assessment Page 3
H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) in the school building and twelve (12)
outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the
Attachment. Readings were collected in the morning and evening. The results are described
below.
Temperature
Indoor dry bulb temperature measurements ranged from 72.1 °F to 87.1 °F. Thirty-one (31) of
the indoor measurements for temperature were below and one (1) was above the range of 73 to
79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the
summer season . The outdoor temperature ranged from 72.1 to 80.6 °F.
Relative Humidity
The relative humidity indoors ranged from 44.1 percent to 47.9 percent. All of the indoor
measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity range was 44.1 to 49.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 421 ppm to 1460 ppm. Five (5) of the
indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level. The outdoor (background)
CO2 concentration was 521 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1221 ppm (background level + 700 ppm). The highest measurement (1460 ppm)
was collected in room # 1005 around 12:00 P.M. with 33 occupants. Levels above the
recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as
an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2
ppm for all readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 29 pg/m^ with an
average 19 pg/m^- All the indoor measurements for PM2.5 were within the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals such as asthmatic people and children. The outdoor respirable particulate
concentrations ranged from 16 pg/m^ to 27 pg/m^ with an average of 22 pg/m^.