Mr. Bernard P. Orlan May 7, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time environmental measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 70.1 °F to 85.1 °F. One hundred and four (104) of the indoor measurements for temperature were below and one (1) was above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Sundard 55- 1992 during the summer season . The outdoor temperature ranged from 71.1 to 72.3 °F.
Relative Humidity
The relative humidity indoors ranged from 43.9 percent to 50.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 45.4 to 49.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 410 ppm to 1260 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 471 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1171 ppm (background level + 700 ppm). The highest measurement (1260 ppm) was collected in room # 905 around 1:10 P.M. with 33 occupants. Levels'above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also Ippm for all readings.
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 19 pg/m^ to 39 pg/m^ with an average 28 pg/m^- All the indoor measurements for PM2.5 were within the NPAAQS of 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 26 pg/m^ to 46 pg/m^ with an average of 34 pg/m^.
CITY_21MC1OO_OO3O7929O
NYC-WTC_000291707
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000399254
Indoor air quality report dated May 7, 2002 for High School project; ATC.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399420
Indoor air quality measurements collected May 20, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291723
Indoor air quality measurements report for HS Leadership & [name], May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291823
lAQ measurements report for HS Leadership, 90 Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291988
ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399348
IAQ measurements collected May 14, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000291723
Indoor air quality measurements report for HS Leadership & [name], May 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399290
Indoor air quality measurements collected May 8, 2002, at the referenced school for BOE evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296893
Indoor air quality measurements at the referenced HS, BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291910
Report of indoor air quality measurements at 90 Trinity Place, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality report dated May 7, 2002 for High School project; ATC.
Similar indexed content
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
Similar indexed content
NYC-WTC_000399420
Indoor air quality measurements collected May 20, 2002, for the High School for Leadership & [name].
Similar indexed content